19

 UG 6970 / 05.12.17 en / 947

Input

  

Nominal voltage U

N

 

DC 24 V

Voltage range: 

 

0.8 ... 1.1 U

N

Nominal consumption:

 

typ. 3.2 W

Short-circuit protection: 

 

Internal PTC

Overvoltage protection: 

 

Internal VDR

Duty-cycle ON button:

 

0.1 s < t

EIN

 < 3 s

Duty-cycle Reset button:

 

> 3 s

Safety function 
Safety mat / safety edge (4)

max. permitted 
safety edge contact resistance:  1000 

Ω

switching current at short circuit:  typ. 15 mA at U

N

Light curtains (8)

control current via S12, S22
e.g. S32, S42: 

typ. 8 mA at U

N

Min. voltage on terminals 
S12, S22 e.g. S32, S42
when relay activated:  

DC 10 V

Output

Contacts

 

2 NO contacts per safety function 

The NO contacts can be used for safe braking.

Thermal current Strom I

th

 

max. 8 A 

   

(see quadratic total current limit curve)

Safety function
E-Stop (1) (6), Safety gate (2) (7),
Exclusive or contacts (5)

Start up at U

N

< 65 ms

Release delay at U

and 

disconnecting the supply:  

< 40 ms

Release delay at U

and 

disconnecting S12,S22 or 

S32, S42: 

< 60 ms

Simultaneity demand:  

< 3 s

Two-hand control (3)

Start up at U

N

:  

< 110 ms

Release delay at U

and 

disconnecting the supply:  

< 40 ms

Release delay at U

and 

disconnecting S12,S22 or

S32, S42: 

< 60 ms

Simultaneity demand:  

< 0,5 s

Safety mat (4)

Start up at U

N

:  

< 85 ms

Release delay at U

and 

disconnecting the supply:  

< 40 ms

Release delay at U

and 

disconnecting S12,S22 or

S32, S42: 

< 60 ms

Light curtains (8)

Start up at U

N

< 35 ms

Release delay at U

and 

disconnecting the supply:  

< 40 ms

Release delay at U

and 

disconnecting S12,S22 or 

S32, S42: 

< 25 ms

Simultaneity demand:  

< 1 s

Switching capacity

to AC 15
NO contacts:  

3 A / AC 230 V  

IEC/EN 60 947-5-1

to DC 13
NO contacts:  

2 A / DC 24 V  

IEC/EN 60 947-5-1

Electrical life

at 5 A, AC 230 V cos 

j

 = 1:  

> 1.5 x 10

5

 switching cycles

Permissible operating frequency 

 

1. safety function:  

max. 1800 switching cycles / h

2. safety function:  

max. 360 switching cycles / h

Short circuit strength

max. fuse rating:  

6 A gG /gL 

IEC/EN 60 947-5-1

Mechanical life: 

 

10 x 10

6

 switching cycles

Semiconductor monitoring output
(not safety): 

 

1 per safety function

   

max. 50 mA DC 24 V, plus switching

   

(see quadratic total current limit curve)

 

Technical Data

Operation mode

With the potentiometer on the front plate the operartion mode can be 
adjustet. The adjustment must be required before energizied. Adjustment 
during energization is not allowed.
Only an automatic start at safety function two-hand control (3) is possible.

Start

Fkt. 1

Fkt. 2

1

MANUAL

MANUAL

2

MANUAL

AUTO

3

AUTO

HAND

4

AUTO

AUTO

5

MANUAL with common 

button

Line fault detection e.g. monitoring of ON-button

If the On-button pressed more than 3 s the adequate output contacts of the 
safety function can't be switch. The output contacts can be energized when 
the On-button pressed again (0.1 s < t

ON

 < 3 s).

A line fault is detected if the On-button more than 10 s is actuated. The 
output contacts of the adeauate safety function can only be energized with 
a reset or re-start with on an off switching of power supply.

Reset and external failures:

The reset input is used to reset external failures (application failures or 
removable external failures as e.g. a line fault on reset button). If the reset 
signal is connected to the input for more than 3 sec the unit unit makes a 
reset. A new reset is only possible when the reset signal had been switched 
off temporarily.
If an external failure occurs because both input channels of a safety function 
did not switch on or off within the simultanious time, a reset is only possible 
if both channels are switched to off state after removing failure cause.
If an external failure occurs in only one safety function, only this function 
will be disconnected. The second safety function still continuous to work.
 

Function setting

The variants with selectable safety functions have 2 potentiometers Fkt.1 
and Fkt.2 to select the required function. The following functions are possible:
 

Fkt. 1  / Fkt. 2

Safety function

1

E-Stop

cross fault detection

2

Safety gate

3

Two-hand control

4

Safety mat / Safety edge

5

Exclusive or contacts

6

E-Stop

without 

cross fault detection

7

Safety gate

8

Light curtain

Practical Notes

Operating Potentiometer

Poti "t

Fkt

Adjustment of delay function

Poti "t

max

Adjustment of time range

Poti "t" 

Fine adjustment at time range

Содержание SAFEMASTER C UG 6970

Страница 1: ...Multifunktionales Sicherheits modul UG 6970 0266691 Datenblatt Betriebsanleitung DEUTSCH E DOLD S HNE KG Postfach 1251 78114 Furtwangen Deutschland Telefon 49 7723 6540 Fax 49 7723 654356 dold relays...

Страница 2: ...dung 6 Blockschaltbild 6 Hinweise 7 Bedienelemente 7 Technische Daten 7 Technische Daten 8 UL Daten 8 Standardtype 8 Bestellbeispiel 9 Vorgehen bei St rungen 9 Wartung und Instandsetzung 9 Kennlinien...

Страница 3: ...en wird wenn die entsprechenden Vorsichtsma nahmen nicht ge troffen werden WARNUNG Bedeutet dass Tod oder schwere K rperverletzung eintreten kann wenn die entsprechenden Vorsichtsma nahmen nicht getro...

Страница 4: ...4 UG 6970 05 12 17 de 947...

Страница 5: ...ger Aufbau zwangsgef hrte Ausgangskontakte Ausgang 2 Schlie er pro Sicherheitsfunktion 1 Halbleitermeldeausgang pro Sicherheitsfunktion LED Anzeigen Betriebsspannung Sicherheitsfunktion 1 2 und Fehler...

Страница 6: ...nktionsdiagramm Gleichzeitigkeits Fehler Querschluss oder Verdrahtungsfehler Leitungsschluss am Ein Taster Poti bzw Einstellungsfehler M10693 Blockschaltbild S22 S12 ST1 t tEin t tdiff t tdiff t tdiff...

Страница 7: ...einstellung Zur Einstellung der Betriebsart Hand oder Automatischer Start ist das Potentiometer Start vorgesehen Dieses Poti befindet sich auf der Front Platte des Ger tes Dabei ist zu beachten dass d...

Страница 8: ...emmenbezeichnung EN 50 005 Leiterbefestigung unverlierbare Schlitzschraube oder Federkraftklemmen Schnellbefestigung Hutschiene IEC EN 60 715 Nettogewicht ca 275 g Ger teabmessungen Breite x H he x Ti...

Страница 9: ...eitsfunktion 0 einstellbar 1 Sicherheitsfunktion 0 einstellbar Klemmenart PC plugin cageclamp abnehmbare Klemmenbl cke mit Feder kraft klemmen PS plugin screw abnehmbare Klemmenbl cke mit Schraubklemm...

Страница 10: ...t gemeinsamen Taster Sicherheitsfunktion 2 siehe rechts Hand Start mit gemeinsamen Taster DC24V 0V A1 A2 ST1 K6 K8 K5 K7 ST2 S42 S41 S31 S32 13 43 23 53 24 54 38 68 14 44 M10516_e K1 K3 K1 K3 K2 K4 K2...

Страница 11: ...Querschlusserkennung SIL 3 PL e Kat 4 Fkt Antivalente Schalter 5 mit Querschlusserkennung SIL 3 PL e Kat 4 Fkt Not Aus 6 ohne Querschlusserkennung SIL 3 PL e Kat 4 1 S21 S22 S11 S12 Schiebeschutzt r...

Страница 12: ...12 UG 6970 05 12 17 de 947 E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com Postfach 1251 Telefon 0 77 23 654 0 Telefax 0 77 23 654 356...

Страница 13: ...Instructions ENGLISH E DOLD S HNE KG P O Box 1251 D 78114 Furtwangen Germany Tel 49 7723 6540 Fax 49 7723 654356 dold relays dold com www dold com Translation of the original instructions SAFEMASTER C...

Страница 14: ...gram 18 Practical Notes 19 Operating Potentiometer 19 Technical Data 19 Technical Data 20 UL Data 20 Standard Type 20 Variants 21 Troubleshooting 21 Maintenance and Repairs 21 Characteristics 21 Appli...

Страница 15: ...ranty DANGER DANGER Indicates that death or severe personal injury will result if proper precautions are not taken WARNING WARNING Indicates that death or severe personal injury can result if proper p...

Страница 16: ...16 UG 6970 05 12 17 en 947...

Страница 17: ...RES S31 S21 ST1 23 53 ST2 S41 S22 38 24 54 68 S42 M10501_a 13 43 K1 K3 K2 K4 23 53 14 44 24 54 K3 K4 K1 K2 68 38 green LED ON on when supply connected red LED ERR on at internal error flashes at exte...

Страница 18: ...S41 S22 S42 23 53 13 43 GND 24 38 68 54 14 44 K1 K3 K2 K4 K1 K2 K3 K4 K2 K4 K1 K3 K3 K4 K1 K2 ON monitoring logic function 1 function 2 overvoltage and short circuit protection Safteyfct 2 automatic s...

Страница 19: ...mA DC 24 V plus switching see quadratic total current limit curve Technical Data Operation mode With the potentiometer on the front plate the operartion mode can be adjustet The adjustment must be req...

Страница 20: ...nical data that is not stated in the UL Data can be found in the technical data section Technical Data UL Data Standard Type General Data Nominal operating mode continuous operation Temperature range...

Страница 21: ...minals PC plug in cage clamp pluggable terminal blocks with cage clamp terminals PS plug in screw pluggable terminal blocks with screw terminals PT plug in Twin cage clamp pluggable terminal blocks wi...

Страница 22: ...page 7 Manual start with common button M10714_c DC24V 0V A1 A2 ST1 K6 K8 K5 K7 ST2 S42 S41 S31 S32 13 43 23 53 24 54 38 68 14 44 K1 K3 K1 K3 K2 K4 K2 K4 On K5 K6 K7 K8 UG6970 S22 S21 S11 S12 Safetyfu...

Страница 23: ...ety mat Safety edge 4 with cross fault detection SIL 3 PL e Cat 4 Fct Exclusive or contacts 5 with cross fault detection SIL 3 PL e Kat 4 Fct E Stop 6 without cross fault detection SIL 3 PL e Cat 4 1...

Страница 24: ...24 UG 6970 05 12 17 en 947 E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com POBox1251 Telephone 49 7723 654 0 Telefax 49 77 23 654 356...

Страница 25: ...nuel d utilisation FRAN AIS E DOLD S HNE KG B P 1251 78114 Furtwangen Allemagne T l 49 7723 6540 Fax 49 7723 654356 dold relays dold com www dold com Traduction de la notice originale SAFEMASTER C Mod...

Страница 26: ...otentiom tre 31 Caract ristiques techniques 31 Caract ristiques techniques 32 Donn es UL 32 Versions standard 32 Variantes 33 Diagnostics des d fauts 33 Entretien et remise en tat 33 Courbes caract ri...

Страница 27: ...que la mort ou des blessures graves vont survenir en cas de non respect des pr cautions demand es AVERTISSEMENT AVERTISSEMENT Indique que la mort ou des blessures graves peuvent survenir si les pr cau...

Страница 28: ...28 UG 6970 05 12 17 fr 947...

Страница 29: ...4 selon EN ISO 13849 1 Valeur limite SIL demand e SIL CL 3 selon IEC EN 62061 Safety Integrity Level SIL 3 selon IEC EN 61508 et IEC EN 61511 selon EN 50156 1 pour installations de chauffage D tectio...

Страница 30: ...38 68 54 14 44 K1 K3 K2 K4 K1 K2 K3 K4 K2 K4 K1 K3 K3 K4 K1 K2 ON protection contre les surtension et courts circuit logique de surveillance fonction 1 fonction 2 Fct de s curit 2 d marrage automatiq...

Страница 31: ...lisation semi conducteurs non s curitaires max 50 mA DC 24 V com front positif voir courbe limite de courant totalisateur Remarques Caract ristiques techniques Mode de service Le commutateur Start est...

Страница 32: ...as sp cifi es ci dessus sont sp cifi es dans les valeurs techniques g n rales Caract ristiques techniques Donn es UL Versions standard Caract ristiques g n rales Type nominal de service service perman...

Страница 33: ...r glable Type de bornes PC plug in cage clamp d brochables avec bornes ressorts PS plug in screw d brochables avec bornes vis PT plug in Twin cage clamp d brochables avec bornes ressorts 2 cond Garni...

Страница 34: ...teur commun fonction de s curit 1 voir droite d marrage manuel avec un commutateur commun fonction de s curit 2 voir droite d marrage manuel avec un commutateur commun M10717_d marche DC24V 0V A1 A2 K...

Страница 35: ...M10775 S22 S11 S12 S12 S1 M11124 S21 S22 S11 S12 M10773 d arr t d urgence S21 Fct Tapis bandeaux de s curit 4 avec d tection des courts circuits transversaux SIL 3 PL e Cat 4 Fct Interrupteur compl m...

Страница 36: ...36 UG 6970 05 12 17 fr 947 E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com B P 1251 T l phone 49 77 23 654 0 T l fax 49 77 23 654 356...

Страница 37: ...24 to 12 2 x 0 2 1 0 mm2 2 x AWG 24 to 18 A 10 mm 1 x 0 2 2 5 mm2 1 x AWG 24 to 12 A 8 mm 1 x 0 2 1 5 mm2 1 x AWG 24 to 16 M10249 A A 7 mm 1 x 0 25 2 5 mm2 1 x AWG 24 to 12 2 x 0 25 1 0 mm2 2 x AWG 2...

Страница 38: ...FR Dimensions dimensions en mm M4345_a M4345_a 35 115 3 0 0 7 122 6 0 0 7 B A 106 9 DE Montage Demontage der PS PC PT Klemmenbl cke EN Mounting disassembly of the PS PC PT terminal blocks FR Montage...

Страница 39: ...ktion an das Ger t Intervall f r zyklische berpr fung der Sicherheitsfunktion Demand to our device based on the evaluated neccessary safety level of the application Intervall for cyclic test of the sa...

Страница 40: ...nformit tserkl rung EN CE Declaration of Conformity FR D claration de conformit europ enne E DOLD S HNE KG D 78114 Furtwangen e mail dold relays dold com internet http www dold com Bregstra e 18 Telef...

Отзывы: