16
BD 5987 / 22.01.19 en / 088A
Input
Nominal voltage U
N
:
AC 24, 42, 48, 110, 127, 230, 240 V
1)
DC 24 V
Voltage range:
AC 0.8 ... 1.1 U
N
at 10% residual ripple:
DC 0.9 ... 1.2 U
N
at 48% residual ripple:
DC 0.8 ... 1.1 U
N
Nominal consumption:
approx. 5.5 VA
Nominal frequency:
50 / 60 Hz
Control voltage at S33:
DC 24 V
Control current
BD 5987.02:
typ. DC 55 mA
BD 5987.02/001 + /301:
typ. DC 45 mA
Minimum voltage at
terminals S12, S22:
DC 21 V with activated device
Recovery time:
0.5 s after release of the e-stop pushbutton
Output
Contacts
BD 5987.02:
2 NO contacts
BD 5987.03:
2 NO contacts, 1 NO contact used for
monitoring
The NO contact 33-34 can only be used for monitoring.
Operate time:
max. 100 ms
BD 5987.02/001 + /301:
with automatic restart approx. 1 s
Release time
2-channel disconnecting in
secondary circuit
(S12, S22 and S23):
50 ms
±
25 %
Opening in supply circuit
BD 5987.02:
350 ms
±
50 %
BD 5987.02/001:
120 ms
±
50 %
BD 5987.02/301:
40 ms
±
50 %
Fault detection time at U
N
:
at 1-channel interruption
at S12:
BD 5987:
typ. 430 ms
BD 5987/001+/201:
typ. 85 ms
at S22 and S23:
50 ms
±
25 %
Contact type:
relay, forcibly guided
Nominal output voltage:
AC 250 V
1)
DC: see arc limit curve
Thermal current I
th
:
see continuous current limit curve
(max. 10 A in one contact path)
Switching capacity
contacts 13/14, 23/24:
to AC 15:
3 A / AC 230V
1)
IEC/EN 60 947-5-1
to AC 15:
6 A / AC 230V
1)
at 0.25 Hz
to DC 13:
2 A / DC 24 V IEC/EN 60 947-5-1
to DC 13:
6 A / DC 24 V at 0.1 Hz
contacts 33/34:
to AC 15:
3 A / AC 230V IEC/EN 60 947-5-1
to DC 13:
2 A / DC 24 V IEC/EN 60 947-5-1
Electrical life
contacts 13/14, 23/24
at AC 230 V, 6 A, cos
ϕ
= 1:
> 5 x 10
5
switching cycles
contacts 33/34
at AC 230 V, 1 A, cos
ϕ
= 1:
> 5 x 10
5
switching cycles
Permissible operating
frequency:
600 switching cycles / h
1)
max. AC 160 V or DC 160V for the variant BD 5987.02/301 when used
in an elevator control acc. to elevator directive 2014/33/EU, if the
BD 5987.02/301 is not installed in a cabinet with prot. degree IP 54 or better.
Short circuit strength
max. fuse rating:
6 A gG / gL
IEC/EN 60 947-5-1
Mechanical life:
10 x 10
6
switching cycles
General Data
Operating mode:
Continuous operation
Temperature range
operation:
- 15 ... + 55
°
C
at max. 90 % humidity
storage :
- 25 ... + 85
°
C
altitude:
< 2.000 m
Clearance and creepage
distances
rated impuls voltage /
pollution degree:
4 kV / 2 (basis insulation) IEC 60 664-1
EMC:
IEC/EN 62 061
Interference suppression:
Limit value class B
EN 55 011
Degree of protection
Housing:
IP 40
IEC/EN 60 529
Terminals:
IP 20
IEC/EN 60 529
Connection Terminals
Terminal designation
Signal description
A1 (+)
+ / L
A2 (-)
- / N
S12, S22, S23, S34, X6, Y2
T12, T22, T34
Inputs
PE (-), S21/PE, S33, X5, Y1
T11, T12, T33
Outputs
13, 14, 23, 24
Forcibly guided NO contacts for
release circuit
33, 34
Indicator output
Notes
Line fault detection at the On pushbutton:
The output contacts cannot be closed if the On pushbutton is already
closed before the voltage is applied to S12, S22 (also in the event of a line
fault at the On pushbutton).
A line fault at the On pushbutton which occurs after activation of the de-
vice is recognized when switching- on takes place again and closing of the
output contacts is then prevented.
If a line fault occurs at the On pushbutton after the voltage is already
present at S12, S22 undesired activation will take place, because this line
fault does not differ from the normal closing function.
The gold-plated contacts of the BD 5987 mean that this module is also
suitable for switching small loads of 1 mVA ... 7 VA, 1 mW ... 7 W in the
range 0.1 ... 60 V, 1 ... 300 mA. The contacts also permit the maximum
switching current. However, since the gold plating will be burnt off at this
current level, the device is no longer suitable for switching small loads
after this.
The PE terminal permits operation of the device in IT systems with insula-
tion monitoring and also serves as a reference point for testing the control
voltage. The internal short-circuit protection will be bridged on DC devices,
if the protective ground is connected to terminal PE.
One or more extension modules BN 5989 or external contactors with for-
cibly guided contacts may be used to multiply the number of contacts of
the emergency stop module BD 5987.
For automatic restart:
S22 must be connected before S12. S12 initiates the automatic restart.
With manual restart it is not necessary to follow this order.
Technical Data
Circuit Diagrams
K3
K2
Y2 PE
A1 Y1
S33
S12
S22
S34
A2
23
24
14
13
S12 S12
S34
S33
S33 S33
A1
(+)
PE
(-)
S22
14 24
Y1
13 23
Y2
A2
(-)
M7375_b
K3
K2
K1
X6 PE
A1 X5
S33
S12
S22
S34
A2
23
24
34
33
14
13
33
S34
S21
/PE
34
X6
X5
A1
(+)
S22
S12
14 24
S23
13 23
S33
A2
(-)
M7378_b
K3
K2
X6 PE
A1 X5
S33
S12
S22
S34
A2
23
24
14
13
S12
S34
S21
/PE
S33
X6
X5
A1
(+)
S22
S12
14 24
S23
13 23
S33
A2
(-)
M7376_b
K3
K2
K1
X6 PE
A1 T11
T33
T12
T22
T34
A2
23
24
34
33
14
13
33
T34
PE
34
X6
T33
A1
(+)
T22
T12
14 24
S23
13 23
T11
A2
(-)
M7379_c
BD 5987.02
BD 5987.03/001
BD 5987.02/001 + /301
BD 5987.03/201