17
BD 5987 / 22.01.19 en / 088A
Housing:
Thermoplastic with V0 behaviour
according to Ul subject 94
Vibration resistance:
Amplitude 0,35 mm IEC/EN 60 068-2-6
frequency 10 ... 55 Hz
Climate resistance:
15 / 055 / 04
IEC/EN 60 068-1
Terminal designation:
EN 50 005
Wire connection:
1 x 4 mm
2
solid or
1 x 2,5 mm
2
stranded ferruled (isolated)
or
2 x 1,5 mm
2
stranded ferruled (isolated)
DIN 46 228-1/-2/-3/-4 or
2 x 2,5 mm
2
stranded ferruled
DIN 46 228-1/-2/-3
Wire fixing:
Plus-minus terminal scews
M3.5 box terminal with wire protection
Fixing torque:
0.8 Nm
Mounting:
DIN rail
IEC/EN 60 715
Weight:
450 g
Dimensions
Width x height x depth:
45 x 74 x 121 mm
Technical Data
Standard Type
BD 5987.02/001 DC 24 V
Article number:
0040954
• Output:
2 NO contacts
• Nominal voltage U
N
:
DC 24 V
• Width:
45 mm
BD 5987.02/61:
with UL approval (Canada/USA)
BD 5987.02/001:
Optionally cross fault monitoring on the
emergency stop loop (see application M6749)
Optionally automatic On function when operating voltage
is applied or after activation by the On pushbutton.
Jumper asignment for functions:
Activation via On pushbutton / or automatic On function:
M8687
On pushbutton
S12-S34 or
S33-S34
Jumper
X5 - X6
Function
The output contacts are switched only
after operation of the On pushbutton.
Line fault monitoring at the On push-
button.
Automatic On function for operating
voltage Off/On or after emergency-
stop release
BD 5987.03/001:
with 2 NO contacts,
1 signalling contact AC/DC 0,1 ... 1 A / 10 ...120 V
BD 5987.03/201
: see BD 5987.03/001,
but with special terminal designation
Jumper asignment for functions:
Activation via On pushbutton / or automatic On function
M8687
On pushbutton
T11-T34 or
T12-T34
Jumper
T33 - X6
Function
The output contacts are switched only
after operation of the On pushbutton.
Line fault monitoring at the On push-
button.
Automatic On function for operating
voltage Off/On or after emergency-
stop release
BD 5987.02/301:
Starting behaviour as with BD 5987.02/001,
shorter release time when opening the supply circuit,
Suitable also for elevators according to EN 81-20/-50,
Complies to the requirements of the directive
2014/33/EU for elevators.
Ordering example for variants
BD 5987 .02 /_ _ _ AC 230 V
50/60 Hz
Nominal frequency
Nominal voltage
Variant, if required
Contacts
Type
Variants
Troubleshooting
Failure
Potential cause
LED "Power" does not light up
Power supply not connected
LED "K2" lights up,
but "K3" remains off
- Safety relay K2 is welded
(replace device)
- A 1-channel switch-off occurred on
S22, T22 e.g. S23
(switch channel off on S12 e.g. T12)
LED "K3" lights up,
but "K2" remains off
- Safety relay K3 is welded
(replace device)
- A 1-channel switch-off occurred on
S12 e.g. T12
(switch channel off on S22, T22 e.g.
S23)
Device cannot be activated
- Safety relay is welded
(replace device)
- Manual start mode:
Line fault on start-button (disconnect
power supply and remove fault)
- Automatic start mode:
X5 - X6 e.g. T33 - X6
are not bridged
Maintenance and repairs
- The device contains no parts that require maintenance.
- In case of failure, do not open the device but send it to manufacturer
for repair.
Nominal voltage U
N
:
AC 24, 42, 48, 110, 127, 230, 240 V
DC 24 V
Ambient temperature:
- 15 … + 55 °C
Switching capacity:
6 A, 250 Vac G.P.
Wire connection:
60°C / 75°C copper conductors only
AWG 18 - 16 Torque 7 lb in
nfo
Technical data that is not stated in the UL-Data, can be found
in the technical data section.
UL-Data