DE
EN
3.2. Flash Codes
The different flash codes are given via the status LED and terminal 1. They signal the present status
of the DFA.
Signal sequence
Flash code
Description
LED off
0
disconnected (blocked)
LED on
1
operating (standard mode)
LED sequence:
0.9 s on / 0.1 s off
2
RCCB error (no tripping)
LED sequence:
0.1 s on / 0.9 s off
3
automatic connection active
LED sequence:
1 s on / 1 s off
4
automatic connection
failed (blocked)
Flash code 2 has the highest priority and can only be reset by briefly switching off the DFA (RESET)
using the rotary switch or disconnecting the operating voltage for a short time.
EN
DE
21
Содержание DFA 2-3
Страница 12: ...4 2 Ma e Doepke 12...