DMP Electronics SecureCom Smart Z-Wave Z-5010T Скачать руководство пользователя страница 18

16 

SecureCom Smart Z-Wave Thermostat Installation Guide

Advanced System Settings Menu

The Advanced System Settings Menu provides for addition system setup options . These settings 

can affect system operation and should only be changed by qualified HVAC installers.
To access the Advanced System Settings menu, first press and hold the 

FAN

 button to get into 

the Setup menu . While in the Setup Menu, press and hold both the 

FAN

 and 

 buttons for 5 

seconds .

• 

Use the 



 buttons to scroll through the menu options to the desired setting .

• 

Press 

SELECT

 (Mode) button to change a setting. Once it begins to flash, use the 



 

buttons to select the desired setting . 

• 

Press the 

SELECT

 button to accept the new setting (flashing will stop).

Feature

Description

Range

Default 

Setting

Test Mode

Test mode shortens the system built-in delays (like 

MOT and MRT)
Y = Test mode on . Reduces all delays to 10 seconds for 

quicker system testing
N = Test mode off . Normal system delays

Y or N

N

Aux Heat 

Enable 

(Heat Pump 

Systems only)

Enables the auxiliary heat operation .
Typically the auxiliary heat will be heat-strips in a 

heat pump system .

Y or N

N

2nd Stage 

Heat Enable

Enables the second stage heat operation

Y or N

N

2nd Stage 

Cool Enable

Enables the second stage cool operation

Y or N

N

Minimum run 

time

Sets the Minimum Run Time (MRT) delay before a 

heating/cooling cycle can turn off .
Sets heating/cooling cycle time . Prevents rapid on/

off cycling .

1-9

3

Minimum Off 

time

Sets the Minimum Off Time (MOT) delay before another 

heating/cooling cycle can begin . Provides compressor 

short cycle protection . “Wait” is displayed on screen 

when active .

5

-

Minutes

5

Heat 

Setpoint 

Max .

Sets the maximum heating setpoint value .
Will not ramp or accept setpoints higher than this 

maximum

55F to 90F
(4C to 43C)

90F 
(32C)

Cool Setpoint 

Min .

Sets the maximum heating setpoint value

60F to 95F
(6C-45C)

60F
(15C)

Heat Blower 

Off Delay

Sets the system blower delay off time after a heat call 

ends (fan purge)

0 to 9 

seconds

0 (off)

Cool Blower
Off Delay

Sets the system blower delay off time after a cool call 

ends (fan purge)

0 to9 

seconds

0 (off)

Содержание SecureCom Smart Z-Wave Z-5010T

Страница 1: ...Installation and operation Guide MODE FAN 74 Off Auto 72H 80c F SecureCom Smart Z Wave Thermostat Model Z 5010T...

Страница 2: ...Menu Mode 12 Menu Mode Navigation 12 System Menu 13 System Type 13 Fan Type For Standard HVAC systems only 13 Changeover Type For Heat Pump HVAC Systems Only 13 Z Wave Installation 14 Inclusion and E...

Страница 3: ...eatures Include A fixed format display with white backlight Heating and cooling setup display options System mode OFF Heat Cool Auto E Heat Fan mode control and display Auto ON Changeover type for Hea...

Страница 4: ...UE RED WHITE ORANGE GREEN YELLOW BLACK BROWN THERMOSTAT BACK PANEL Y2 Y1 G RC C RH W1W2 0 INTERNAL RC RH JUMPER C WIRE IS NOT REQUIRED FOR BATTERY OPERATION C WIRE IS REQUIRED FOR 24VAC OPERATION FOR...

Страница 5: ...HVAC SYSTEM BLUE RED WHITE ORANGE GREEN YELLOW BLACK BROWN THERMOSTAT BACK Y2 Y1 G RC C RH W1W2 0 C WIRE IS NOT REQUIRED FOR BATTERY OPERATION NOTE MOST HEAT PUMP SYSTEMS DO HAVE THE C WIRE AND THERM...

Страница 6: ...re typically a red wire Battery Power Powering the thermostat from batteries does not require a C wire connection DO NOT install batteries if the thermostat is powered by 24VAC They are not required f...

Страница 7: ...e old thermostat and will help with troubleshooting later if needed Terminal Typical Wire Color Function Y YELLOW Cool W WHITE Heat G GREEN Fan R RED 24VAC Return C BLUE 24V Common typically BLUE When...

Страница 8: ...back panel of thermostat Mount the thermostat back panel on the wall See Figure 4 1 Use the two 2 wall anchors and two 2 Phillips screws provided to mount the back panel 2 Level as needed Figure 4 Mou...

Страница 9: ...as these are internally jumpered together If installing a Standard HVAC system connect the wires from the HVAC system to the corresponding terminals on the thermostat back terminal block Use the table...

Страница 10: ...able below as a guideline for connecting the wires Wire Terminal Y2 Connect to the Y2 terminal 2 stage systems only Y or Y1 Connect to the Y1 terminal G Connect to the G terminal COOL RC Connect to RC...

Страница 11: ...erminal Y Connect to the Y1 terminal G Connect to the G terminal R Connect to either R terminal C Connect to the C terminal The C wire 24VAC common Heat Pump systems typically have the C wire connecte...

Страница 12: ...l at indents on bottom of case See Figure 12 Install the four 4 type AA batteries and assemble as shown in Figure 13 Figure 12 Opening Battery Case Cover Figure 13 Battery Installation MODE FAN BODY F...

Страница 13: ...with the first press Wait Mode The thermostat has a Minimum Off Time MOT delay after any heating or cooling cycle ends This delay prevents rapid heating cooling cycles and also provides short cycle pr...

Страница 14: ...buttons to scroll through the following menu items Figure 15 Menu Navigation The following menu items are displayed in order SETUP user preference settings SYSTEM HVAC system setup Z WAVE install unin...

Страница 15: ...on the heating system type For Gas heat select GAS This is the default setting For Electric heat press the buttons to change to ELECTRIC Press SELECT to set Press DONE to exit Changeover Type For Hea...

Страница 16: ...Steps three 3 through 7 to re try connecting 9 When the thermostat information is received by the system the keypad panel beeps once and displays DEVICE FOUND 10 Once added the panel keypad displays t...

Страница 17: ...current time 7 Press SELECT DONE DONE INFO Menu The INFO menu displays information about the thermostat Use the buttons to scroll through the various items MODEL Z 5010T VERSION Thermostat firmware ve...

Страница 18: ...ys Y or N N Aux Heat Enable Heat Pump Systems only Enables the auxiliary heat operation Typically the auxiliary heat will be heat strips in a heat pump system Y or N N 2nd Stage Heat Enable Enables th...

Страница 19: ...egrees 2 Heating Stage 2 Off Threshold Sets the delay from setpoint that stage 2 heating stops Stage 2 turns off at setpoint Delta Stage 2 0 to 6 degrees 0 Aux Heat On Threshold Sets the delta from se...

Страница 20: ...blinking System is ON and cooling Minimum Run Time MRT delay is active NOTE Degrees C Celsius are shown in 5 degree increments Degrees F Fahrenheit are shown in 1 degree increments Staging Indicators...

Страница 21: ...onal system mode Heat E for Emergency Heat will be displayed if the HVAC System Type is set to Heat Pump If there is a compressor failure with the Heat Pump system setting the mode to Emergency Heat w...

Страница 22: ...he heating setpoint lower if the cooling setpoint is set below the current heating setpoint A 3 degree separation is maintained between the heating and cooling setpoints The same is true for raising t...

Страница 23: ...Use the FAN button to select the HVAC system s fan mode Auto Fan automatically operated by the HVAC system normal setting On Manual Fan mode Fan stays on until mode is changed back to Auto independent...

Страница 24: ...the backlight timeout can be set to 0 which will keep the backlight on continuously SENSOR CALIBRATION Change the temperature calibration by 7 degrees Press the UP or DOWN arrow buttons to change to t...

Страница 25: ...ELECT DONE DONE INFO Menu The INFO menu displays information about the thermostat Use the buttons to scroll through the various items MODEL Z 5010T VERSION Thermostat firmware version ZWAVE Z Wave fir...

Страница 26: ...Accuracy 1 F 0 5 C Remote Control Via Z Wave Standard Gas Electric HVAC Systems 2 stage heating 2 stage cooling Heat Pump HVAC System 3 stage heating 2 stage cooling Thermostat Connections Uses stand...

Страница 27: ...er s authority to operate the equipment Industry Canada Notices IC 9374A TBZ48 This device complies with Industry Canada license exempt RSS standard s Operation is subject to the following two conditi...

Страница 28: ...LT 1423 15265 2015 Digital Monitoring Products Inc Information furnished by DMP is believed to be accurate and reliable This information is subject to change without notice...

Отзывы: