Series Communicator Install/Programming Guide 

Digital Monitoring Products

21

AREA INFORMATION 

Area Information

14.1 

Area Information

This section allows you to assign functions to the burglary area of the communicator. 

All non-24-hour zones must be assigned to an active area. See the section on Zone 

Information.

14.2 

Area Number

Only Area 1 is available to program. 

14.3 

Area Name

Default Area Name is AREA 1. To change the area name in the system, press any Select 

key and then enter up to 16 characters for the new name. Press COMMAND to continue.  

Refer to the Entering Alpha Characters section.

14.4 

Automatic Arming

Select YES to allow this area to arm automatically according to the opening and closing 

schedule.

If Closing Check is selected as YES, the automatic arming does not take place until the 

expiration of a 10-minute Closing Check delay. If the area has been disarmed outside a 

schedule, the Closing Check delay occurs one hour after the area is disarmed.

At arming, faulted zones are handled according to the option selected in Bad Zones. If 

a Closing report is sent, the user number is indicated as SCH on the SCS-1R or SCS-VR 

Receivers

. Select NO to disable automatic arming for this area. Default is NO.

14.5 

Automatic Disarming

NO disables automatic disarming by schedule for this area. Select YES to allow this area 

to automatically disarm according to a schedule. If an Opening report is sent to the 

receiver, the user number is indicated as SCH.

Zone Information

15.1 

Zone Information

This allows you to define the operation of each protection zone used in the system.

15.2 

Zone Number

The c

ommunicator has four zones to program. Enter the number of the zone you intend 

to program. Press COMMAND to enter a zone name. Refer to the Enter Alpha Characters 

section.

15.3 

Zone Name

Press any Select key and enter up to 16 characters for the zone name. A name must be 

given to each zone in the system. This name can be displayed at the keypads when the 

zone is bad or viewed in Display Events. The zone name is also sent to the receiver as 

part of a zone event report.

A zone that is not part of the system must be marked *UNUSED*. To mark a zone unused, 

de lete the old name by pressing any Select key, then press the COMMAND key. The pro-

grammer auto matically pro grams the name as * UNUSED *. If you selected ZONES? NO 

YES to clear the 

communicator

’s memory during Initialization, the zones will already be 

marked * UNUSED *. See the Initialization section.

15.4 

Zone Type

The Zone Type defines the response of the 

communicator to the zone being open or 

short. Refer to the Appendix for zone type defaults and descriptions.

When you assign a Zone Type to a zone, responses are made automatically for the zone. 

There are 11 Zone Types to choose from including Blank. The func tional details of each 

response are described in Zone Type Defaults in the Appendix.

To select a new Zone Type, press any Select key. The display lists the four Zone Types 

shown below. When the Zone Type you want to select displays, press the Select key 

below the name.

Blank, Night, Day, or Exit. Press COMMAND to display additional zone types.

Fire, Panic, Emergency, or Supervisory. Press COMMAND to display additional zone types.

Auxiliary 1, Auxiliary 2, Fire Verify, or Arming. Press the Back Arrow key to display the 

previous zone types.

If you select Blank, Night, Day, Exit, Auxiliary 1, or Auxiliary 2 as the Zone Type, the 

zone must be assigned to an area. If you select Fire, Panic, Emergency, or Supervisory as 

the Zone Type, these are 24-hour zones that are always armed and no area assignment is 

needed. Press COMMAND to continue.

Refer to the Appendix for zone type specifications and descriptions.

AREA INFORMATION

AREA 1

AUTO ARM 

NO

 YES

AUTO DIS 

NO

 YES

ZONE INFORMATION

ZONE NO: -

* UNUSED *

ZONE TYPE: BLANK

ZONE INFORMATION

A1  A2  AR FV

FI  PN  EM SV

AREA NO: -

--  NT  DY EX

Содержание CELLCOMSL SERIES

Страница 1: ...CELLCOMSL SERIES CELLULAR ALARM COMMUNICA TOR INSTALL PROGRAMMING GUIDE...

Страница 2: ...e installer may find the following booklet prepared by the Federal Communications Commission helpful How to identify and Resolve Radio TV Interference Problems This booklet is available from the U S G...

Страница 3: ...s 6 3 4 Virtual Keypad App 6 Z Wave Setup 7 User Code Level Master only 7 5 1 Add Z Wave Devices ADD 7 5 2 List Z Wave Devices LIST 7 5 3 RENAME Z Wave Devices 7 5 4 STATUS of Z Wave Devices 8 5 5 Rem...

Страница 4: ...Reports 15 8 10 Supervisory Trouble Reports 15 8 11 Opening Closing and User Reports 15 8 12 Test Report 15 8 13 First IP Address 15 8 14 First IP Port 16 8 15 Second IP Address 16 8 16 Second IP Por...

Страница 5: ...rmation 21 14 1 Area Information 21 14 2 Area Number 21 14 3 Area Name 21 14 4 Automatic Arming 21 14 5 Automatic Disarming 21 Zone Information 21 15 1 Zone Information 21 15 2 Zone Number 21 15 3 Zon...

Страница 6: ...stics program 26 18 4 Using the 984 Command Function 26 CELL 26 18 5 Using the Walk Test 26 Walk Test 26 Trip Counter for Walk Test STD 26 Test End Warning 27 Failed Zones Display 27 18 6 Cross Zoning...

Страница 7: ...applications What is Included The CellComSL Series Cellular Alarm Communicator includes the following PCB with Enclosure 3 7 VDC 800 mAh Lithium Ion Battery Hardware Pack System Components 1 1 Termin...

Страница 8: ...2 Battery Connection BAT J26 Installation Safety Ground Yourself Before Handling the Communicator To discharge static touch any grounded metal such as the control panel enclosure before touching the...

Страница 9: ...t board and is used to reset the communicator microprocessor After resetting the communicator begin programming within 30 minutes If you wait longer than 30 minutes reset the communicator again 1 6 Lo...

Страница 10: ...holes See Figure 11 Mount the enclosure in a secure dry place away from metal objects to protect the communicator from damage due to tampering or the elements It is not necessary to remove the PCB wh...

Страница 11: ...2 CONTROL PANEL TIP CONTROL PANEL RING 12 VDC Aux Output Ground Burglary Panel The panel or separate power supply must be 12 Volt Regulated and Power Limited Telephone Jack Connector Z1 Z2 BELL BELL I...

Страница 12: ...llComSLCZ only configure Rooms CellComSLCZ only turn Outputs on and off and add edit or remove Users Use 18 22 AWG for Power Supply connection Z3 Z4 Z4 GND OUT1 OUT2 CONTROL PANEL TIP CONTROL PANEL RI...

Страница 13: ...S BUTTON ON DEVICE TO ADD displays press the program button on the Z Wave device See the Z Wave device s documentation for more information 5 When the device information is received by the system the...

Страница 14: ...en removed 5 6 Favorites FAV Z Wave devices can be grouped together to create a Favorite This option allows you to program up to 20 Favorites in your system and then ADD EDIT OR REMOVE up to 25 Z Wave...

Страница 15: ...he new temperature and press COMMAND 6 Press any Select key and the keypad displays FAN SETTING 7 Press any Select key and ON AUTO displays Press the Select key under the desired new setting to change...

Страница 16: ...User Menu 2 Press COMMAND until ZWAVE SETUP displays 3 Press any Select key The keypad displays ADD LIST REMOVE 4 Press COMMAND again to display FAV XFER REDISC Select XFER The keypad displays XFER W...

Страница 17: ...der of the Introduction explains starting and ending a programming session 6 2 Getting Started Ground Yourself Before Handling the Panel Touch any grounded metal before touching the communicator to di...

Страница 18: ...ads Each time you need to press a Select key the keypad displays the function or options above one of the keys or in the Select Area Displaying choices above individual Select keys or in Select Areas...

Страница 19: ...ions are either shown as a number a blank or a NO or YES To change a number or blank to a new number press any top row Select key or touch any Select Area The current option is replaced with a dash Pr...

Страница 20: ...O leaves existing zone information intact YES sets all zones in the system to UNUSED 7 6 Clear Communication NO Leaves existing communication programming intact YES Clears communication to factory def...

Страница 21: ...heck in option Default is 0 Note If Cell Check in option is used additional cell charges may apply 8 7 Fail Time Fail Time allows the SCS 1R or SCS VR receiver to miss a defined number of check ins be...

Страница 22: ...eports to be sent to this receiver Default is NO 8 19 Supervisory Trouble Reports YES enables Supervisory Trouble Trouble Restoral Force Armed Late to Close and Fault reports to be sent to this receiv...

Страница 23: ...or arming disarming authorization 9 8 Destination 3 Enter the third destination cell phone number 9 9 Destination 3 User Number If Destination 3 is a cellular number enter the user s User Number for a...

Страница 24: ...a zone that has restored from an alarm or trouble is disarmed Twenty four hour zones send restorals immediately System Options 12 1 System Options This section allows you to select system wide parame...

Страница 25: ...sed Bypassed zones are auto matically reset when the area they are assigned to is disarmed All 24 hour zones are reset when any area of the system is dis armed A programming Stop operation restores a...

Страница 26: ...f the output is turned off manually the cut off time is reset The Cutoff Time can be 1 15 minutes Enter 0 zero to provide continuous output Note The output is cutoff within 60 seconds of the programme...

Страница 27: ...ect key and enter up to 16 characters for the zone name A name must be given to each zone in the system This name can be displayed at the keypads when the zone is bad or viewed in Display Events The z...

Страница 28: ...reported and the zone is disabled until you disarm the area from either a keypad or Remote Link computer 15 8 Next Zone When YES is selected the programming for the zone terminates and the display ret...

Страница 29: ...nction the zone remains normal for one hour and the Reset Swinger Bypass is YES If the zone trips fewer than the specified times within one hour of the first trip the bypass trip counter returns to 0...

Страница 30: ...ws you to program a special code that will then be required to gain access to the communicator s internal Programmer through the keypad Changing the Lockout Code You can change this code at any time t...

Страница 31: ...System Recently Armed report S78 is sent when a burglary zone goes into alarm within two minutes of the system being armed 18 3 Diagnostics Function The communicator contains a Diagnostics function t...

Страница 32: ...atus List display 18 4 Using the 984 Command Function When not in the Programming Menu the function 984 COMMAND can be entered at the keypad and a remote options menu appears This menu contains the fo...

Страница 33: ...RM report is sent to the receiver for zone 1 and zone 2 Note To operate correctly all cross zone zones need to be programmed as the same zone type 18 7 Zone Type Descriptions This section describes ap...

Страница 34: ...a primary controller The XFER feature allows an existing 3rd party network to be transferred into the CellComSLCZ The CellComSLCZ can support Z Wave products from different vendors and product categor...

Страница 35: ...CellComSL Series Communicator Install Programming Guide Digital Monitoring Products 29 APPENDIX...

Страница 36: ...803 8877 14185 Specifications Primary Power 12VDC Current Draw 180 mA Standby 120 mA Dimension Housing 5 5 W x 3 75 L x 1 H Color White Accessories XX 0000 Replacement Rechargeable Battery Listings an...

Отзывы: