DMP Electronics CELLCOMSL SERIES Скачать руководство пользователя страница 15

CellComSL

 

Series Communicator Install/Programming Guide 

Digital Monitoring Products

9

Z-WAVE SETUP

7.   Select ADD and the first Z-Wave device stored in the system that has not already been added to this 

Favorite is 

displayed. Remaining devices can be viewed by pressing the 

COMMAND key.

8.   Press any Select key to assign the displayed device to the 

Favorite. The device name and the current device 

settings display. When added to a Favorite, a Z-Wave device can be programmed to respond to various ON/

OFF/LOCK/UNLOCK/HEAT/COOL commands based on your desired settings. To change a device setting, See 

Device Settings in Favorites.

5.9  Device Settings in FAVORITES

Lights

1. 

Press any Select key at SETTING: and ON  OFF  DIM displays. Press the Select key under the desired setting.

2.   For ON or OFF setting, when selected, the 

Favorite name and the next 

Z-Wave device stored in the system 

displays.

3.   For DIM setting, DIM LEVEL: with the current setting displays. To change the setting, press any Select key and 

enter the new level (1 - 10) and Press COMMAND.

4. 

The Favorite name and the next 

Z-Wave device stored in the system displays.

Locks

1. 

 Press any Select key at SETTING: and LOCK  UNLOCK displays. To  

change the setting, press the Select 

key under the new setting.

2. 

The Favorite name and the next 

Z-Wave device stored in the system displays.

Thermostats

1. 

 Press any Select key at SYSTEM: and OFF  CL  HT displays. To change the setting of OFF, COOL or HEAT, press 

the Select key under the new setting.

2.  Select OFF to display FAN SETTING:.
3.  Press any Select key and ON  AUTO displays. Press the Select key under the desired new setting to change.
4.  Select CL to display COOL.

5. 

To change the setting, press any Select key, enter the new temperature and press COMMAND.

6. 

 Press any Select key and the keypad displays

 

FAN SETTING:.

7.  Press any Select key and ON  AUTO displays. Press the Select key under the desired new setting to change.
8.  Select HT to display HEAT.
9.  To change the setting, press any Select key and enter the new temperature and Press COMMAND.
10.   Press any Select key and the keypad displays

 

FAN SETTING:.

11. 

Press any Select key and ON  AUTO displays. Press the Select key under the desired new setting to change.

12. 

The Favorite name and the next 

Z-Wave device stored in the system displays.

Note:  A maximum of 25 devices can be assigned to each Favorite. When attempting to add a device and the 

maximum number of devices has been assigned, FAVORITE FULL is displayed. No additional Z-Wave devices 

may be added to this Favorite, however a new Favorite may be created and devices added to the new 

Favorite.

5.10  EDIT Devices in FAVORITES

1. 

Access the User Menu.

2. 

Press 

COMMAND until ZWAVE SETUP? displays.

3.  Press any Select key. The keypad displays ADD  LIST  REMOVE.
4. 

Press 

COMMAND again to display FAV  XFER  REDISC. Select FAV and FAVORITE NUMBER: - is displayed.

5. 

Enter a Favorite number between 1 and 20 and press COMMAND.

6.  The Favorite number and name displays. Press 

COMMAND and the Favorite Name and ADD  EDIT  REMOVE 

displays.

7.  Select EDIT and the first Z-Wave device stored in the 

Favorite displays. Remaining devices can be viewed by 

pressing the 

COMMAND key.

Note:

  

 Z-Wave devices are displayed by device type; Lights first, followed Locks, and Thermostats last. By pressing 

the 

COMMAND key you can scroll through the devices assigned to the selected 

Favorite.

8.  Press any Select key to display the device name and the setting for the device.
9.  To change the setting, See Device Settings in Favorites.
10.  Once the device settings have been entered, the 

Favorite name and the next 

Z-Wave device stored in the 

selected Favorite displays.

Содержание CELLCOMSL SERIES

Страница 1: ...CELLCOMSL SERIES CELLULAR ALARM COMMUNICA TOR INSTALL PROGRAMMING GUIDE...

Страница 2: ...e installer may find the following booklet prepared by the Federal Communications Commission helpful How to identify and Resolve Radio TV Interference Problems This booklet is available from the U S G...

Страница 3: ...s 6 3 4 Virtual Keypad App 6 Z Wave Setup 7 User Code Level Master only 7 5 1 Add Z Wave Devices ADD 7 5 2 List Z Wave Devices LIST 7 5 3 RENAME Z Wave Devices 7 5 4 STATUS of Z Wave Devices 8 5 5 Rem...

Страница 4: ...Reports 15 8 10 Supervisory Trouble Reports 15 8 11 Opening Closing and User Reports 15 8 12 Test Report 15 8 13 First IP Address 15 8 14 First IP Port 16 8 15 Second IP Address 16 8 16 Second IP Por...

Страница 5: ...rmation 21 14 1 Area Information 21 14 2 Area Number 21 14 3 Area Name 21 14 4 Automatic Arming 21 14 5 Automatic Disarming 21 Zone Information 21 15 1 Zone Information 21 15 2 Zone Number 21 15 3 Zon...

Страница 6: ...stics program 26 18 4 Using the 984 Command Function 26 CELL 26 18 5 Using the Walk Test 26 Walk Test 26 Trip Counter for Walk Test STD 26 Test End Warning 27 Failed Zones Display 27 18 6 Cross Zoning...

Страница 7: ...applications What is Included The CellComSL Series Cellular Alarm Communicator includes the following PCB with Enclosure 3 7 VDC 800 mAh Lithium Ion Battery Hardware Pack System Components 1 1 Termin...

Страница 8: ...2 Battery Connection BAT J26 Installation Safety Ground Yourself Before Handling the Communicator To discharge static touch any grounded metal such as the control panel enclosure before touching the...

Страница 9: ...t board and is used to reset the communicator microprocessor After resetting the communicator begin programming within 30 minutes If you wait longer than 30 minutes reset the communicator again 1 6 Lo...

Страница 10: ...holes See Figure 11 Mount the enclosure in a secure dry place away from metal objects to protect the communicator from damage due to tampering or the elements It is not necessary to remove the PCB wh...

Страница 11: ...2 CONTROL PANEL TIP CONTROL PANEL RING 12 VDC Aux Output Ground Burglary Panel The panel or separate power supply must be 12 Volt Regulated and Power Limited Telephone Jack Connector Z1 Z2 BELL BELL I...

Страница 12: ...llComSLCZ only configure Rooms CellComSLCZ only turn Outputs on and off and add edit or remove Users Use 18 22 AWG for Power Supply connection Z3 Z4 Z4 GND OUT1 OUT2 CONTROL PANEL TIP CONTROL PANEL RI...

Страница 13: ...S BUTTON ON DEVICE TO ADD displays press the program button on the Z Wave device See the Z Wave device s documentation for more information 5 When the device information is received by the system the...

Страница 14: ...en removed 5 6 Favorites FAV Z Wave devices can be grouped together to create a Favorite This option allows you to program up to 20 Favorites in your system and then ADD EDIT OR REMOVE up to 25 Z Wave...

Страница 15: ...he new temperature and press COMMAND 6 Press any Select key and the keypad displays FAN SETTING 7 Press any Select key and ON AUTO displays Press the Select key under the desired new setting to change...

Страница 16: ...User Menu 2 Press COMMAND until ZWAVE SETUP displays 3 Press any Select key The keypad displays ADD LIST REMOVE 4 Press COMMAND again to display FAV XFER REDISC Select XFER The keypad displays XFER W...

Страница 17: ...der of the Introduction explains starting and ending a programming session 6 2 Getting Started Ground Yourself Before Handling the Panel Touch any grounded metal before touching the communicator to di...

Страница 18: ...ads Each time you need to press a Select key the keypad displays the function or options above one of the keys or in the Select Area Displaying choices above individual Select keys or in Select Areas...

Страница 19: ...ions are either shown as a number a blank or a NO or YES To change a number or blank to a new number press any top row Select key or touch any Select Area The current option is replaced with a dash Pr...

Страница 20: ...O leaves existing zone information intact YES sets all zones in the system to UNUSED 7 6 Clear Communication NO Leaves existing communication programming intact YES Clears communication to factory def...

Страница 21: ...heck in option Default is 0 Note If Cell Check in option is used additional cell charges may apply 8 7 Fail Time Fail Time allows the SCS 1R or SCS VR receiver to miss a defined number of check ins be...

Страница 22: ...eports to be sent to this receiver Default is NO 8 19 Supervisory Trouble Reports YES enables Supervisory Trouble Trouble Restoral Force Armed Late to Close and Fault reports to be sent to this receiv...

Страница 23: ...or arming disarming authorization 9 8 Destination 3 Enter the third destination cell phone number 9 9 Destination 3 User Number If Destination 3 is a cellular number enter the user s User Number for a...

Страница 24: ...a zone that has restored from an alarm or trouble is disarmed Twenty four hour zones send restorals immediately System Options 12 1 System Options This section allows you to select system wide parame...

Страница 25: ...sed Bypassed zones are auto matically reset when the area they are assigned to is disarmed All 24 hour zones are reset when any area of the system is dis armed A programming Stop operation restores a...

Страница 26: ...f the output is turned off manually the cut off time is reset The Cutoff Time can be 1 15 minutes Enter 0 zero to provide continuous output Note The output is cutoff within 60 seconds of the programme...

Страница 27: ...ect key and enter up to 16 characters for the zone name A name must be given to each zone in the system This name can be displayed at the keypads when the zone is bad or viewed in Display Events The z...

Страница 28: ...reported and the zone is disabled until you disarm the area from either a keypad or Remote Link computer 15 8 Next Zone When YES is selected the programming for the zone terminates and the display ret...

Страница 29: ...nction the zone remains normal for one hour and the Reset Swinger Bypass is YES If the zone trips fewer than the specified times within one hour of the first trip the bypass trip counter returns to 0...

Страница 30: ...ws you to program a special code that will then be required to gain access to the communicator s internal Programmer through the keypad Changing the Lockout Code You can change this code at any time t...

Страница 31: ...System Recently Armed report S78 is sent when a burglary zone goes into alarm within two minutes of the system being armed 18 3 Diagnostics Function The communicator contains a Diagnostics function t...

Страница 32: ...atus List display 18 4 Using the 984 Command Function When not in the Programming Menu the function 984 COMMAND can be entered at the keypad and a remote options menu appears This menu contains the fo...

Страница 33: ...RM report is sent to the receiver for zone 1 and zone 2 Note To operate correctly all cross zone zones need to be programmed as the same zone type 18 7 Zone Type Descriptions This section describes ap...

Страница 34: ...a primary controller The XFER feature allows an existing 3rd party network to be transferred into the CellComSLCZ The CellComSLCZ can support Z Wave products from different vendors and product categor...

Страница 35: ...CellComSL Series Communicator Install Programming Guide Digital Monitoring Products 29 APPENDIX...

Страница 36: ...803 8877 14185 Specifications Primary Power 12VDC Current Draw 180 mA Standby 120 mA Dimension Housing 5 5 W x 3 75 L x 1 H Color White Accessories XX 0000 Replacement Rechargeable Battery Listings an...

Отзывы: