Digital Monitoring Products, Inc. | 734N Series Installation and Programming Guide
25
PROGRAM THE 734N SERIES MODULE
When you program the 734N Series module, you must use a keypad connected to the
programming header and set to address 1. For 12 V applications, connect the keypad to
the module using a Model 330 4‑wire harness. For 24 V applications, connect the keypad
to the module using a Model 330‑24 4‑wire programming harness with in‑line resistor.
Caution:
Do not connect a keypad using a standard Model 330 harness if using a 24 V
power supply! Damage to the keypad could occur.
You can also program the module from an XR150/XR550 Series panel. If you choose to
program the 734N from the panel, all future programming should be performed through
the panel. The panel’s programming overrides any programming performed from a
keypad connected to the 734N. While the module is in programming mode, it will not be
able to communicate with the panel.
Caution:
OSDP readers can only be programmed locally from the module with a
keypad. To properly bond the reader to the module, the 734N must be new or
initialized and the reader must be new or factory reset. After programming is
complete and the keypad is disconnected, the reader is bonded to the module and
cannot be reprogrammed with a different secure key until it is factory reset by the
manufacturer.