22
734N Installation and Programming Guide | Digital Monitoring Products, Inc.
ZONE 2 BYPASS TIME
Enter the number of seconds to elapse before the bypass timer
expires. The range is from 20-250 seconds. Press any select key or
area to enter the number of seconds. The default is
40
. Figure 11
shows how the bypass option works.
ZONE 2 BYPASS
TIME:
40
5 Second
Strike
40-Second Zone 2 Bypass
entry/exit timer.
10 seconds before
the bypass time expires,
the device beeps if
the door is still open.
End of
timer.
40
Seconds
A zone open/short is
indicated if the door
remains open.
Figure 11: Zone 2 Bypass Timeline
RELOCK ON ZONE 2 CHANGE
Selecting
YES
turns the relay off when zone 2 changes state.
Selecting
NO
leaves the relay on when zone 2 changes state.
Turning off the relay at Door Closed allows a long strike time to be
automatically ended and relocks the door. The default is
NO
.
RELOCK ON ZONE 2
CHANGE?
NO
YES