Digital Monitoring Products, Inc. | 734N Installation and Programming Guide
21
ACTIVATE ZONE 2 BYPASS
Select
YES
to activate the zone 2 bypass operation. Selecting
NO
allows standard zone operation on zone 2. The default is
NO
.
If the door being released by the 734N module is protected (contact
installed), a programmable bypass entry/exit timer can be provided
by connecting its contact wiring to the 734N module zone 2. When
the on-board Form C relay activates and the user opens the door
connected to zone 2, the zone is delayed for the number of seconds
programmed in
ZONE 2 BYPASS TIME
allowing the user to enter/exit
during an armed period.
If zone 2 does not restore (door closed) within the programmed time,
the piezo sounds every other second during the last ten seconds. If
zone 2 restores prior to the end of the programmed time, the piezo
silences. If the zone does not restore before the programmed time, the
734N ends the bypass and indicates the open or short zone condition
to the panel.
ACTIVATE ZONE 2
BYPASS?
NO
YES