FT7000, RACK MONITOR MANUAL 11033PA-ATEX
LINX overfill detection system.
NO ONBOARD MONITOR
ONBOARD MONITOR
5-WIRE SENSORS
2-WIRE SENSORS
5-WIRE SENSORS
2-WIRE SENSORS
NO GROUND
DEVICE ENABLED
NO
YES
NO
NO
1+ GROUND DEVICE
ENABLED
YES
YES
YES
YES
Accessories
The FT7000 monitor can be set up to utilize either a Deadman switch or Emergency Stop switch. The
switch must be Normally Open. A deadman switch will require the driver to actively hold a switch during
the entirety of the loading process. Releasing the switch while loading will cause the FT7000 to go non-
permissive.
Technical Specifications
MIN
MAX
NOMINAL
INGRESS PROTECTION (IP)
IP54
SUPPLY VOLTAGE
110VAC
240VAC
SUPPLY FREQ
50Hz
60Hz
SUPPLY POWER
13W (8 probes) 6W (IDLE)
OPERATING TEMPERATURE
-20C/-4F
60C/140F
HUMIDITY
0%
100%
LENGTH
333mm/13.13”
WIDTH
316mm/12.44”
DEPTH
104mm/4.09”
WEIGHT
14.5KG/32LBS
RS-485 TERMINATION
(optional)
120Ω
RELAY CONTACT RATING
240VAC 5A
ACCEPTABLE WIRE GAUGE
12AWG
18AWG
LID SCREW TORQUE
35 lb-ft