FT7000, RACK MONITOR MANUAL 11033PA-ATEX
Replacement Parts
•
CORROSION INHIBITOR – Replacement Part Number: 10977
This rack monitor comes with a corrosion inhibitor located inside of the enclosure. This inhibitor
must be removed from its’ plastic packaging once the rack is properly installed. The inhibitor
should be replaced every 12 months for continual protection of the monitor’s electronics. This
will help to extend the life of the rack monitor.
•
FUSES – Replacement Part Number: 10974/10975
The stated rating for all replaceable fuses should not be exceeded, however if a fuse does burn
out, replace the fuse with a Dixon brand or Dixon approved fuse. Replacing the fuse with a non-
approved fuse may alter the normal operation of the monitor or impede the intrinsic safety of
the device.
To replace the fuse:
1. Use a flat-head screwdriver to push down and turn the fuse holder cap approximately 1/8
th
of
a turn.
2. The cap will pop out, allowing the cap and internal fuse to be removed.
3. Separate the bad fuse from the cap, discard the old fuse, and replace with an approved fuse.
4. Insert the fuse and cap into the fuse-holder.
5. Use a flat-head screwdriver to push down and turn the cap into place.