FT7000, RACK MONITOR MANUAL 11033PA-ATEX
Mains supply must be fed from a circuit breaker protected line. The circuit breaker in-line with FT7000
must have a breaking capacity of 5,000A or more.
Terminals showing this symbol must we wired using cables rated for at least 194°F (90°C). Les
terminaux avec ce symbole doivent être branché avec des câbles approuvé a au moins 194°F (90 °C)