Installation and Operating Instructions 

21.

 

TROUBLESHOOTING  

Problem 

Possible reason 

Notes 

Display flashing 

HA

 

 

Temperature too high. 

 

Check cooling system. 

 

Check alarm settings. 

Display flashing 

LA

 

 

Temperature too low. 

 

Check cooling system. 

 

Check alarm settings. 

Display flashing 

HA2

 

 

Condenser temperature too high. 

 

Check condenser cooling system. 

 

Check alarm settings. 

Display flashing 

LA2

 

 

Condenser temperature too low. 

 

Check condenser cooling system. 

 

Check alarm settings. 

Display flashing 

P1

 

 

Fault with thermostat probe. 

 

Wrong type of probe fitted 
(NTC/PTC). 

 

Check probe connections and resistance value. 

 

Change probe type or alter a parameter 

PbC

Display flashing 

P2

 

 

Fault with evaporator probe. 

 

Wrong type of probe fitted 
(NTC/PTC). 

 

Parameter 

tC

 has been set to 4, 5 

or 6 without evaporator probe 
fitted. 

 

Check probe connections and resistance value. 

 

Change probe type or alter parameter 

PbC

 

Fit evaporator probe or alter parameter 

tC

 

Display flashing 

P3

 

 

Fault with third probe. 

 

Wrong type of probe fitted 
(NTC/PTC). 

 

Parameter 

tC

 has been set to 6 

without third probe fitted. 

 

Check probe connections and resistance value. 

 

Change probe type or alter parameter 

PbC

 

Fit evaporator probe or alter parameter 

tC

 

Display flashing 

EE

 

Data corruption. 

Check for electrical spikes and interference. Fit filters DIXL930 & DIXL932. 
Ensure probe cables are separated from power cables. Re-check all parameter 
settings. Replace controller if still not working.  

Display flashing 

dA

 

Door has been left open too long. 

Shut the door. 

Display flashing 

EA

 

A non-serious external alarm has been 
detected by the digital input. 

Trace and rectify the external problem. 

Display flashing 

bAL

 

A serious external alarm has been 
detected by the digital input. 

Trace and rectify the external problem. 

Buttons will not 
work 

Buttons have been locked. 

Unlock buttons by pressing both 

UP

 & 

DOWN

 buttons until display flashes 

Pon

Parameter cannot 
be adjusted over its 
full range 

Some other parameter is conflicting and 
preventing further adjustment. 

Check other parameter settings. 

Power on but no 
output operates 

Small LED’s 

flashing 

Anti-short cycle delay in progress, all 
relays being held off until it expires. 

Wait or adjust parameters 

AC

 or 

odS

Evaporator fan short 
cycling 

Parameter 

FSt

 set too low. 

Adjust 

FSt

 to a higher setting. During commissioning, set it above ambient until 

pull down is complete, then re-set to a more suitable temperature. 

 

22.

 

CHANGE OVER FROM F TO C OR VIS-VERSA 

1.  Hold  the  Set  &  Down  (n)  buttons,  until  HY  is  displayed,  release  both  buttons  then  hold  the  Set  and  Down  (n)  buttons  until  Pr2  is 
displayed. Release the buttons. 
2. Scroll with the up button to CF, then press and release Set. Change the 1 to 0, then press and release Set. 
3. Scroll down and adjust the ALL, ALU, FST, AFH, ALH, LS, US, rES as well as the HY. 
4. Let the control time out to the temp display. 
Adjust the Set temp by holding the Set until the C or F starts to flash, adjust the set point.

 

 

23.

 

ENTER YOUR SETTINGS HERE FOR FUTURE REFERENCE 

Label 

Description 

Edit 

Original 

Vis. 
Level 

Min 

Max 

Comment 

tC 

Parameter map selection 

 

Pr2 

 

PbC 

Kind of probe 

 

ntC 

Pr2 

 

 

 

Содержание UNIVERSAL XR60CX

Страница 1: ...nning with the minimum of fuss Just follow these 5 simple steps STEP 1 Install the new Universal XR per the installation instructions included with the controller STEP 2 Turn on power THEN WITHIN 1 MINUTE COMPLETE STEPS 3 4 AND 5 STEP 3 Press the SET and DOWN key for 3 seconds and the controller will automatically recognise and adjust itself to the type of probes connected The display briefly show...

Страница 2: ...oling Electric or Hot Gas Defrost Temperature Ended TC6 Low Temp Elec Or Hot Gas Defrost Temp Ended Fan Control TC7 Open Map to be Configured for any application Actual Label on The Control in the Box Load1 is always Comp or Heat Load2 is OAA and Load3 is OAb Parameter tC Type of Control Models Replaced Required probes 1 On Off thermostat Heating XR110C XR01CX XR10C XR10CX x 1 2 Off cycle defrost ...

Страница 3: ... 4 F 2 0 C 4 F 2 0 C 4 F 2 0 C 4 F 2 0 C 4 F 2 0 C 4 F Minimum Set Point limit LS 55 C to Set Point 67 F to Set Point 50 0 C 58 F 50 0 C 58 F 50 0 C 58 F 50 0 C 58 F 50 0 C 58 F 50 0 C 58 F 50 0 C 58 F Maximum Set Point limit US Set Point to 150 C Set Point to 302 F 50 0 C 122 F 50 0 C 122 F 50 0 C 122 F 50 0 C 122 F 50 0 C 122 F 50 0 C 122 F 50 0 C 122 F Anti short cycle delay AC 0 to 50 min 1 1 ...

Страница 4: ...probe presence P2P N 0 evaporator probe not present Y 1 evaporator probe present 1 1 1 1 1 Evaporator probe calibration OE 12 0 to 12 0 C 21 to 21 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F Third probe presence P3P n 0 third probe not present Y 1 third probe present 1 1 1 1 1 1 1 Third probe calibration 03 12 0 to 12 0 C 21 to 21 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0...

Страница 5: ...0 0 0 Low temperature alarm of condenser AL2 55 to 150 C 67 to 302 F 40 C 40 F 40 C 40 F 40 C 40 F 40 C 40 F 40 C 40 F 40 C 40 F 40 C 40 F High temperature alarm of condenser AU2 55 to 150 C 67 to 302 F 110 C 230 F 110 C 230 F 110 C 230 F 110 C 230 F 110 C 230 F 110 C 230 F 110 C 230 F Differential for temperature condenser alarm recovery AH2 0 1 to 25 5 C 1 to 45 F 5 C 5 F 5 C 5 F 5 C 5 F 5 C 5 F...

Страница 6: ...ay 0 to 50min minimum interval between the compressor stop and the next possible restart ACI Second compressor start delay 0 to 255sec ALP Probe selection for temperature alarms 0 P1 Room Probe 1 P2 Evaporator Probe 2 P3 Display Probe 3 P4 Hot Key Connector Probe Condenser Alarm Probe ALC Temperature alarm configuration rE Related to Set Point Ab Absolute Note Relative means alarms are linked to t...

Страница 7: ...ner TDF Defrost type 0 El electrical heater 1 rE hot gas compressor runs during defrost FDT Drain down time 0 to 255min drain down time Runs concurrently with Fnd Fan delay after defrost time Both fan and compressor are off during this time period DPO First defrost after power on 0 Y immediately 1 n after the idF interval time FNC Fan operating mode 0 C_n cycles on off with the compressor OFF duri...

Страница 8: ...If there is a P1 probe failure the controller will automatically cycle the compressor on off according to Con CoF to maintain basic cooling CoF is the compressor OFF time TBA Alarm muting 0 n Alarm relay remains active when alarm buzzer is muted 1 Y Alarm relay is cancelled when alarm buzzer is muted I2F Second digital input operating mode configures the second digital input function 0 Starts a de...

Страница 9: ...pressor keeps on working if a low temperature alarm at the condenser is active 1 Y the compressor is switched off while the low temperature alarm is active The regulation will restart after elapsing AC delay time AC2 Compressor off when an high temperature alarm of the condenser is active 0 n the compressor keeps on working if a low temperature alarm at the condenser is active 1 Y the compressor i...

Страница 10: ...will be displayed Exit programming mode press together to return to normal display 7 PROGRAMMING MODE 7 1 USER PROGRAMMING LEVEL PR1 To enter programming level Pr1 user programming level keep both SET and DOWN buttons pressed for 3 sec The first parameter label will appear Browse parameter list by using the UP or DOWN keys Press SET to see a parameter s current value and UP or DOWN keys to alter i...

Страница 11: ...ON FUNCTION MEANING ON Light AUX output enabled ON Cooling enabled FLASHING Anti short cycle delay in progress ON Fan enabled FLASHING Delay time on fan activation is running Fnd 0 ON Defrost in progress FLASHING Drip time in progress Fdt 0 or delay on start defrosting is running dSd 0 ON Auxiliary output activated ON Energy Saving activated ON Thermostat override enabled ON ALARM signal when in p...

Страница 12: ...ossible to network the Universal XR60CX to the XWEB monitoring systems or a third party system The controller has TTL communications that can be converted with the XJ485CX key The key is connected to the control via the HOT KEY port with a small 5 wire cable It is then possible to set a unique address via the Adr parameter Then using a two wire communications daisy chain the controls can be monito...

Страница 13: ... hole and fixed using the special brackets supplied Ambient temperature for correct operation is 32 to 140 F Avoid places subject to strong vibrations corrosive gases excessive dirt or humidity 20 to 85 non condensing RH is the recommended working range Make sure air can freely circulate through the cooling holes slots at the rear side of the controller 18 ELECTRICAL CONNECTIONS The instrument is ...

Страница 14: ...orking Display flashing dA Door has been left open too long Shut the door Display flashing EA A non serious external alarm has been detected by the digital input Trace and rectify the external problem Display flashing bAL A serious external alarm has been detected by the digital input Trace and rectify the external problem Buttons will not work Buttons have been locked Unlock buttons by pressing b...

Страница 15: ...AF Defrost delay after fast freezing 2 Pr2 0 255 idF Interval between defrost cycles 6 Pr1 0 250 dSd Start defrost delay 0 Pr2 0 255 dFP Probe selection for first defrost 3 Pr2 MdF Maximum length for first defrost 30 Pr1 0 255 dtE Defrost termination temperature first evaporator 46 Pr1 67 122 dSP Probe selection for second defrost 0 Pr2 MdS Maximum length for second defrost 0 Pr2 0 255 dtS Defrost...

Страница 16: ... alarm delay 0 Pr2 0 255 odC Compressor and fan status when the door is open 0 Pr2 oAA First output configuration 0 Pr2 oAb Second output configuration 3 Pr2 AoP Alarm relay polarity 0 Pr2 dot Temperature alarm exclusion with door open 20 Pr2 0 255 rrd Regulation restart with door open alarm 0 Pr2 AP2 Probe selection for condenser temperature alarms 0 Pr2 AL2 Condenser low temperature alarm 0 Pr2 ...

Страница 17: ...Universal XR 17 17 UXR01212015_REV1 4mm Installation and Operating Instructions 905 Waverly Ave Holtsville NY 11742 631 207 1200 f 631 207 0900 www weissinstruments com sales weissinstruments com ...

Отзывы: