background image

 

Universal-XR 

                     10/17 

UXR01212015_REV1.4mm 

 

    

 

Installation and Operating Instructions 

6.

 

BUTTONS AND THEIR FUNCTIONS  

6.1

 

SINGLE BUTTON FUNCTIONS 

Table 5: single button functions 

BUTTON 

FUNCTION 

 

Type Controller menu: 

keep this button pressed for at least 3 sec within 1 min after power on to enter the “Type Controller Menu” (

tC

). 

AUX output control: 

Switches the AUX relay output (if enabled as such).

 

 

 

Manual Defrost:

 keep this button pressed for 3 s to start a manual defrost cycle. The defrost icon will illuminate.  

(Not possible if parameter 

tC

 = 1 ). 

 

Display current set point:

 after pressing and releasing this button, the set point will be displayed for 5 sec. This will not allow the set point to 

be altered. 

Changing set point value:

 

keep this button pressed for at least 2 sec. Set point change mode is entered indicated by the small led’s flashing.  

Change the set point using the 

UP

 and 

DOWN

 buttons. The new value can be stored either by pressing 

SET 

button (the instrument restores 

temperature display) or by waiting the exit time-out to expire (15 sec). 

 

(UP):

 to see the max stored temperature; in programming mode it browses the parameter codes or increases the displayed value. 

 

(DOWN):

 to see the min stored temperature; in programming mode it browses the parameter codes or decreases the displayed value. 

Keep press 3sec just after powering on the device (and within the first 60sec) to start automatic probe recognising. 

 

Energy Saving:

 Allows the control to use the HES offset parameter to change the set point. 

 

6.2

 

BUTTON COMBINATION FUNCTIONS 

Table 6: button combination functions 

COMBINATION 

FUNCTION 

 

 

 

Lock & unlock the keyboard:

 keeping both buttons pressed for 3 sec will lock or unlock the keyboard. The display 

will flash 

PoF

 or 

Pon

 for a few seconds to confirm locking or unlocking respectively. 

 

+

 

 

 

Enter programming mode:

 keep both buttons pressed for 3 sec, release them and then press them again for 8 sec. 

The first label of 

Pr2 

level will be displayed. 

 

+

 

 

 

Exit programming mode:

 press together to return to normal display. 

 

7.

 

PROGRAMMING MODE  

7.1

 

USER PROGRAMMING LEVEL 

 PR1 

To enter programming level 

Pr1 

(user programming level), keep both 

SET 

and 

DOWN 

buttons pressed for 3 sec. The first parameter label will 

appear. Browse parameter list by using the 

UP

 or 

DOWN

 keys. Press 

SET

 

to see a parameter’s current value and 

UP

 or 

DOWN

 keys to alter its 

value. Press 

SET

 to confirm change (the display will blink for 3 sec and then the next parameter will appear) or by waiting for the menu timeout to 

expire (15 sec). If no parameter is available for changes in 

Pr1 

level, a 

noP

 label will be show. 

 

7.2

 

PROTECTED PROGRAMMING LEVEL 

 PR2 (ALL VISIBLE PARAMETERS CAN BE FOUND HERE) 

First enter 

Pr1 

level (as described above) then with any parameter label displayed keep both 

SET 

and 

DOWN 

buttons pressed for 8 sec.

 

The first 

parameter label will appear. Browse parameter list  by using the 

UP

 or 

DOWN

 keys. Press 

SET

 

to see a parameter’s current value and 

UP

 or 

DOWN

 keys to alter its value. Press 

SET

 to confirm change (the display will blink for 3 sec and then the next parameter will appear) or by waiting 

for the menu timeout to expire (15 sec).  
From 

Pr2 

level  it  is  also  possible  to  add  or  remove  any  parameter  to / from 

Pr1

 by pressing both 

SET

 & 

DOWN

 while its label is displayed.  

Accessibility of any particular parameter via 

Pr1 

level is confirmed by the alarm LED lighting up while its label is displayed 

 

WARNING:

 if no button is pressed for 15 seconds, any modified value will be stored into memory and the controller will return to the normal display 

mode. 

8.

 

HOT KEY PROGRAMMING 

Once a control has been programmed, it is possible to save the program from that control to a HOT KEY for programming another control or backup 
of the program.  

8.1

 

HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD) 

1.

 

Program one controller with the front keypad. 

2.

 

When the controller is ON

, insert the “

Hot key

” and push 

o

 key; the 

"uPL" 

message appears followed a by flashing 

“End”

 

3.

 

Push “

SET”

 key and the 

End

 will stop flashing. 

4.

 

Turn OFF the instrument and remove the 

“Hot Key”, 

then turn it ON again. 

Содержание UNIVERSAL XR60CX

Страница 1: ...nning with the minimum of fuss Just follow these 5 simple steps STEP 1 Install the new Universal XR per the installation instructions included with the controller STEP 2 Turn on power THEN WITHIN 1 MINUTE COMPLETE STEPS 3 4 AND 5 STEP 3 Press the SET and DOWN key for 3 seconds and the controller will automatically recognise and adjust itself to the type of probes connected The display briefly show...

Страница 2: ...oling Electric or Hot Gas Defrost Temperature Ended TC6 Low Temp Elec Or Hot Gas Defrost Temp Ended Fan Control TC7 Open Map to be Configured for any application Actual Label on The Control in the Box Load1 is always Comp or Heat Load2 is OAA and Load3 is OAb Parameter tC Type of Control Models Replaced Required probes 1 On Off thermostat Heating XR110C XR01CX XR10C XR10CX x 1 2 Off cycle defrost ...

Страница 3: ... 4 F 2 0 C 4 F 2 0 C 4 F 2 0 C 4 F 2 0 C 4 F 2 0 C 4 F Minimum Set Point limit LS 55 C to Set Point 67 F to Set Point 50 0 C 58 F 50 0 C 58 F 50 0 C 58 F 50 0 C 58 F 50 0 C 58 F 50 0 C 58 F 50 0 C 58 F Maximum Set Point limit US Set Point to 150 C Set Point to 302 F 50 0 C 122 F 50 0 C 122 F 50 0 C 122 F 50 0 C 122 F 50 0 C 122 F 50 0 C 122 F 50 0 C 122 F Anti short cycle delay AC 0 to 50 min 1 1 ...

Страница 4: ...probe presence P2P N 0 evaporator probe not present Y 1 evaporator probe present 1 1 1 1 1 Evaporator probe calibration OE 12 0 to 12 0 C 21 to 21 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F Third probe presence P3P n 0 third probe not present Y 1 third probe present 1 1 1 1 1 1 1 Third probe calibration 03 12 0 to 12 0 C 21 to 21 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0...

Страница 5: ...0 0 0 Low temperature alarm of condenser AL2 55 to 150 C 67 to 302 F 40 C 40 F 40 C 40 F 40 C 40 F 40 C 40 F 40 C 40 F 40 C 40 F 40 C 40 F High temperature alarm of condenser AU2 55 to 150 C 67 to 302 F 110 C 230 F 110 C 230 F 110 C 230 F 110 C 230 F 110 C 230 F 110 C 230 F 110 C 230 F Differential for temperature condenser alarm recovery AH2 0 1 to 25 5 C 1 to 45 F 5 C 5 F 5 C 5 F 5 C 5 F 5 C 5 F...

Страница 6: ...ay 0 to 50min minimum interval between the compressor stop and the next possible restart ACI Second compressor start delay 0 to 255sec ALP Probe selection for temperature alarms 0 P1 Room Probe 1 P2 Evaporator Probe 2 P3 Display Probe 3 P4 Hot Key Connector Probe Condenser Alarm Probe ALC Temperature alarm configuration rE Related to Set Point Ab Absolute Note Relative means alarms are linked to t...

Страница 7: ...ner TDF Defrost type 0 El electrical heater 1 rE hot gas compressor runs during defrost FDT Drain down time 0 to 255min drain down time Runs concurrently with Fnd Fan delay after defrost time Both fan and compressor are off during this time period DPO First defrost after power on 0 Y immediately 1 n after the idF interval time FNC Fan operating mode 0 C_n cycles on off with the compressor OFF duri...

Страница 8: ...If there is a P1 probe failure the controller will automatically cycle the compressor on off according to Con CoF to maintain basic cooling CoF is the compressor OFF time TBA Alarm muting 0 n Alarm relay remains active when alarm buzzer is muted 1 Y Alarm relay is cancelled when alarm buzzer is muted I2F Second digital input operating mode configures the second digital input function 0 Starts a de...

Страница 9: ...pressor keeps on working if a low temperature alarm at the condenser is active 1 Y the compressor is switched off while the low temperature alarm is active The regulation will restart after elapsing AC delay time AC2 Compressor off when an high temperature alarm of the condenser is active 0 n the compressor keeps on working if a low temperature alarm at the condenser is active 1 Y the compressor i...

Страница 10: ...will be displayed Exit programming mode press together to return to normal display 7 PROGRAMMING MODE 7 1 USER PROGRAMMING LEVEL PR1 To enter programming level Pr1 user programming level keep both SET and DOWN buttons pressed for 3 sec The first parameter label will appear Browse parameter list by using the UP or DOWN keys Press SET to see a parameter s current value and UP or DOWN keys to alter i...

Страница 11: ...ON FUNCTION MEANING ON Light AUX output enabled ON Cooling enabled FLASHING Anti short cycle delay in progress ON Fan enabled FLASHING Delay time on fan activation is running Fnd 0 ON Defrost in progress FLASHING Drip time in progress Fdt 0 or delay on start defrosting is running dSd 0 ON Auxiliary output activated ON Energy Saving activated ON Thermostat override enabled ON ALARM signal when in p...

Страница 12: ...ossible to network the Universal XR60CX to the XWEB monitoring systems or a third party system The controller has TTL communications that can be converted with the XJ485CX key The key is connected to the control via the HOT KEY port with a small 5 wire cable It is then possible to set a unique address via the Adr parameter Then using a two wire communications daisy chain the controls can be monito...

Страница 13: ... hole and fixed using the special brackets supplied Ambient temperature for correct operation is 32 to 140 F Avoid places subject to strong vibrations corrosive gases excessive dirt or humidity 20 to 85 non condensing RH is the recommended working range Make sure air can freely circulate through the cooling holes slots at the rear side of the controller 18 ELECTRICAL CONNECTIONS The instrument is ...

Страница 14: ...orking Display flashing dA Door has been left open too long Shut the door Display flashing EA A non serious external alarm has been detected by the digital input Trace and rectify the external problem Display flashing bAL A serious external alarm has been detected by the digital input Trace and rectify the external problem Buttons will not work Buttons have been locked Unlock buttons by pressing b...

Страница 15: ...AF Defrost delay after fast freezing 2 Pr2 0 255 idF Interval between defrost cycles 6 Pr1 0 250 dSd Start defrost delay 0 Pr2 0 255 dFP Probe selection for first defrost 3 Pr2 MdF Maximum length for first defrost 30 Pr1 0 255 dtE Defrost termination temperature first evaporator 46 Pr1 67 122 dSP Probe selection for second defrost 0 Pr2 MdS Maximum length for second defrost 0 Pr2 0 255 dtS Defrost...

Страница 16: ... alarm delay 0 Pr2 0 255 odC Compressor and fan status when the door is open 0 Pr2 oAA First output configuration 0 Pr2 oAb Second output configuration 3 Pr2 AoP Alarm relay polarity 0 Pr2 dot Temperature alarm exclusion with door open 20 Pr2 0 255 rrd Regulation restart with door open alarm 0 Pr2 AP2 Probe selection for condenser temperature alarms 0 Pr2 AL2 Condenser low temperature alarm 0 Pr2 ...

Страница 17: ...Universal XR 17 17 UXR01212015_REV1 4mm Installation and Operating Instructions 905 Waverly Ave Holtsville NY 11742 631 207 1200 f 631 207 0900 www weissinstruments com sales weissinstruments com ...