Installation and Operating Instructions 

-

 

tbA = n

: the alarm relay will remain active until the alarm condition is rectified; 

-

 

tbA = Y

: the alarm relay de-activates when the buzzer is muted. 

 In either case, the display will flash an alarm label until the condition is rectified. 

15.2

 

ALARM “EE”

 

The Dixell Universal-XR is provided with an in

ternal watchdog verifying data and memory integrity. Alarm “

EE

” will flash after detecting a failure in data 

or in the internal memory. In this case, the alarm output is enabled. 

WHAT TO DO 

1.

 

Cancel the alarm by pressing a key.  

2.

 

Check the value of all parameters and restore correct values when wrong. 

3.

 

Check the correct instrument operation and in case of further errors replace it. 

15.3

 

ALARM RECOVERY 

Probe alarms “

P1

”, “

P2

” and “

P3

” start 30 seconds after a fault in probe is detected; they automatically stop 30 sec

onds after the probe restarts normal operation. Check 

connections before replacing the probe. 

Temperature alarms “

HA

” and “

LA

” automatically stop as soon as the thermostat temperature returns to normal values and when defrost starts. Temperature alar

ms 

HA2

” and “

LA2

” automatically stop as soon as the condenser temperature returns to normal values.

 

16.

 

REMOVING SECURITY LEVEL PROTECTION  

It is possible to allow access to any parameter from 

Pr1 

level. To do this, go into 

Pr2

 as previously described. Scroll to the label of the parameter you require and then 

press the 

SET

 and 

DOWN

 buttons in quick succession. The decimal point LED will be on indicating that access to this particular parameter is now possible from 

Pr1

 

level. Its label will now appear when in 

Pr1

 programming level and its value can be altered. To restore security level protection, use the same procedure (the decimal 

point LED will go out after pressing both buttons). 

17.

 

MOUNTING 

The Universal-XR should be mounted in a panel, in a 29

mm (1.14”)

 x 71mm (2.8

”)

 hole, and fixed using the special brackets supplied. Ambient temperature for correct 

operation is 32 to 140°F. Avoid places subject to strong vibrations, corrosive gases, excessive dirt or humidity (20 to 85% non-condensing RH is the recommended 
working range). Make sure air can freely circulate through the cooling holes slots at the rear side of the controller. 

18.

 

ELECTRICAL CONNECTIONS 

The instrument is provided with screw terminal block to connect cables with a cross section up to 2.5 mm

2

. Before connecting cables make sure the 

power supply complies with the instrument’s requirements. Separate the probe cables from the power supply cables, from the ou

tputs and from the 

power connections. Do not exceed the maximum current rating for each relay; in case of heavier loads use a suitable external relay. 

19.

 

PROBES 

It is recommended to place the thermostat probe away from rapid air streams to correctly measure the average room temperature. Place the defrost 
termination probe among the evaporator fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during defrost, 
to prevent premature defrost termination. 

20.

 

TECHNICAL DATA 

Housing:   

 

 

Self-extinguishing ABS

 

Size:   

 

 

 

 

Frontal 32x74 mm; depth 70mm 

Mounting: 

 

 

 

 

Panel mounting in a 71x29 mm panel cut-out 

Frontal protection: 

 

 

IP65 

Connections:  

 

 

 

Screw terminal block 

 2.5 mm

2

 wiring 

Power supply: 

 

 

 

120Vac, -10% +15% or 230Vac, -10% +15%

 

Power absorption:    

 

4 VA max

 

Display:

    

 

 

 

3 digits, red LED, 14.2mm high  

Inputs:

 

 

 

 

 

a maximum of 3 temperature probes, PTC or NTC type. 

Probes (supplied):

 

 

 

2 x NTC, range-50 TO 110°C (-58 to 230°F) with 1.5-meter (4.98

) cables

 

Relay outputs: 

 

 

 

 

 

Compressor:

   

 

SPST relay 16FLA / 96LRA, 250Vac

 

 

Defrost: 

 

 

 

SPDT relay 10A, 250Vac

 

 

Fans: 

 

 

 

SPST relay 5A, 250Vac

 

Other output:

 

 

 

 

Buzzer for acoustic signalling of alarms  

Data storing: 

 

 

 

Non-volatile memory (EEPROM) 

Ambient temperature:   

 

 

0 to 60°C (32 to 140°F) 

Ambient humidity:

    

 

 

20 to 85% (non-condensing) 

Storage temperature:   

 

 

-30 to 85°C (-22 to 185°F) 

Operating range:  

 

 

 

PTC: 

-50 to 150°C (-58 to 302°F); 

NTC: 

-50 to 110°C (-40 to 230°F) 

Resolution:  

 

 

 

0.1°C or 1°F (selectable) 

Accuracy at 25°C: 

 

 

 

(range -40 to 50°C) 

0.5 °C 

1 digit 

 
 
 
 
 

 

Содержание UNIVERSAL XR60CX

Страница 1: ...nning with the minimum of fuss Just follow these 5 simple steps STEP 1 Install the new Universal XR per the installation instructions included with the controller STEP 2 Turn on power THEN WITHIN 1 MINUTE COMPLETE STEPS 3 4 AND 5 STEP 3 Press the SET and DOWN key for 3 seconds and the controller will automatically recognise and adjust itself to the type of probes connected The display briefly show...

Страница 2: ...oling Electric or Hot Gas Defrost Temperature Ended TC6 Low Temp Elec Or Hot Gas Defrost Temp Ended Fan Control TC7 Open Map to be Configured for any application Actual Label on The Control in the Box Load1 is always Comp or Heat Load2 is OAA and Load3 is OAb Parameter tC Type of Control Models Replaced Required probes 1 On Off thermostat Heating XR110C XR01CX XR10C XR10CX x 1 2 Off cycle defrost ...

Страница 3: ... 4 F 2 0 C 4 F 2 0 C 4 F 2 0 C 4 F 2 0 C 4 F 2 0 C 4 F Minimum Set Point limit LS 55 C to Set Point 67 F to Set Point 50 0 C 58 F 50 0 C 58 F 50 0 C 58 F 50 0 C 58 F 50 0 C 58 F 50 0 C 58 F 50 0 C 58 F Maximum Set Point limit US Set Point to 150 C Set Point to 302 F 50 0 C 122 F 50 0 C 122 F 50 0 C 122 F 50 0 C 122 F 50 0 C 122 F 50 0 C 122 F 50 0 C 122 F Anti short cycle delay AC 0 to 50 min 1 1 ...

Страница 4: ...probe presence P2P N 0 evaporator probe not present Y 1 evaporator probe present 1 1 1 1 1 Evaporator probe calibration OE 12 0 to 12 0 C 21 to 21 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F Third probe presence P3P n 0 third probe not present Y 1 third probe present 1 1 1 1 1 1 1 Third probe calibration 03 12 0 to 12 0 C 21 to 21 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0 F 0 0 C 0...

Страница 5: ...0 0 0 Low temperature alarm of condenser AL2 55 to 150 C 67 to 302 F 40 C 40 F 40 C 40 F 40 C 40 F 40 C 40 F 40 C 40 F 40 C 40 F 40 C 40 F High temperature alarm of condenser AU2 55 to 150 C 67 to 302 F 110 C 230 F 110 C 230 F 110 C 230 F 110 C 230 F 110 C 230 F 110 C 230 F 110 C 230 F Differential for temperature condenser alarm recovery AH2 0 1 to 25 5 C 1 to 45 F 5 C 5 F 5 C 5 F 5 C 5 F 5 C 5 F...

Страница 6: ...ay 0 to 50min minimum interval between the compressor stop and the next possible restart ACI Second compressor start delay 0 to 255sec ALP Probe selection for temperature alarms 0 P1 Room Probe 1 P2 Evaporator Probe 2 P3 Display Probe 3 P4 Hot Key Connector Probe Condenser Alarm Probe ALC Temperature alarm configuration rE Related to Set Point Ab Absolute Note Relative means alarms are linked to t...

Страница 7: ...ner TDF Defrost type 0 El electrical heater 1 rE hot gas compressor runs during defrost FDT Drain down time 0 to 255min drain down time Runs concurrently with Fnd Fan delay after defrost time Both fan and compressor are off during this time period DPO First defrost after power on 0 Y immediately 1 n after the idF interval time FNC Fan operating mode 0 C_n cycles on off with the compressor OFF duri...

Страница 8: ...If there is a P1 probe failure the controller will automatically cycle the compressor on off according to Con CoF to maintain basic cooling CoF is the compressor OFF time TBA Alarm muting 0 n Alarm relay remains active when alarm buzzer is muted 1 Y Alarm relay is cancelled when alarm buzzer is muted I2F Second digital input operating mode configures the second digital input function 0 Starts a de...

Страница 9: ...pressor keeps on working if a low temperature alarm at the condenser is active 1 Y the compressor is switched off while the low temperature alarm is active The regulation will restart after elapsing AC delay time AC2 Compressor off when an high temperature alarm of the condenser is active 0 n the compressor keeps on working if a low temperature alarm at the condenser is active 1 Y the compressor i...

Страница 10: ...will be displayed Exit programming mode press together to return to normal display 7 PROGRAMMING MODE 7 1 USER PROGRAMMING LEVEL PR1 To enter programming level Pr1 user programming level keep both SET and DOWN buttons pressed for 3 sec The first parameter label will appear Browse parameter list by using the UP or DOWN keys Press SET to see a parameter s current value and UP or DOWN keys to alter i...

Страница 11: ...ON FUNCTION MEANING ON Light AUX output enabled ON Cooling enabled FLASHING Anti short cycle delay in progress ON Fan enabled FLASHING Delay time on fan activation is running Fnd 0 ON Defrost in progress FLASHING Drip time in progress Fdt 0 or delay on start defrosting is running dSd 0 ON Auxiliary output activated ON Energy Saving activated ON Thermostat override enabled ON ALARM signal when in p...

Страница 12: ...ossible to network the Universal XR60CX to the XWEB monitoring systems or a third party system The controller has TTL communications that can be converted with the XJ485CX key The key is connected to the control via the HOT KEY port with a small 5 wire cable It is then possible to set a unique address via the Adr parameter Then using a two wire communications daisy chain the controls can be monito...

Страница 13: ... hole and fixed using the special brackets supplied Ambient temperature for correct operation is 32 to 140 F Avoid places subject to strong vibrations corrosive gases excessive dirt or humidity 20 to 85 non condensing RH is the recommended working range Make sure air can freely circulate through the cooling holes slots at the rear side of the controller 18 ELECTRICAL CONNECTIONS The instrument is ...

Страница 14: ...orking Display flashing dA Door has been left open too long Shut the door Display flashing EA A non serious external alarm has been detected by the digital input Trace and rectify the external problem Display flashing bAL A serious external alarm has been detected by the digital input Trace and rectify the external problem Buttons will not work Buttons have been locked Unlock buttons by pressing b...

Страница 15: ...AF Defrost delay after fast freezing 2 Pr2 0 255 idF Interval between defrost cycles 6 Pr1 0 250 dSd Start defrost delay 0 Pr2 0 255 dFP Probe selection for first defrost 3 Pr2 MdF Maximum length for first defrost 30 Pr1 0 255 dtE Defrost termination temperature first evaporator 46 Pr1 67 122 dSP Probe selection for second defrost 0 Pr2 MdS Maximum length for second defrost 0 Pr2 0 255 dtS Defrost...

Страница 16: ... alarm delay 0 Pr2 0 255 odC Compressor and fan status when the door is open 0 Pr2 oAA First output configuration 0 Pr2 oAb Second output configuration 3 Pr2 AoP Alarm relay polarity 0 Pr2 dot Temperature alarm exclusion with door open 20 Pr2 0 255 rrd Regulation restart with door open alarm 0 Pr2 AP2 Probe selection for condenser temperature alarms 0 Pr2 AL2 Condenser low temperature alarm 0 Pr2 ...

Страница 17: ...Universal XR 17 17 UXR01212015_REV1 4mm Installation and Operating Instructions 905 Waverly Ave Holtsville NY 11742 631 207 1200 f 631 207 0900 www weissinstruments com sales weissinstruments com ...

Отзывы: