• Connect ducts to air inlet, considering:
- Duct diameter, length, and material type will effect performance;
- Use smooth bore ducting wherever possible as flexible ducts can have up to three times more airflow resistance;
- Inlet ducts should be full diameter, and changes in section or size should be gradual;
•
Connect power as outlined in
APPENDIX 1: Electrical Diagram [230/460/575v] 3-Phase Power
.
•
Ensure that motor rotation is clockwise when looking top-down from unit.
• For the WX-6500, the motor and the auxiliary vent fan are shipped separately from the main cabinet. Once
reinstalled the electrical connection to the main control box must be made as per the provided wiring diagram
• The scrubber is designed to accommodate an auxiliary vent fan that operates when the scrubber is not in
operation. Its function is to vent the air and gases from the scrubber. The fan should exhaust outdoors. If the
fan is to exhaust indoors it is important to check with local regulations and test the exhaust air as required.
• Ensure that the backdraft damper is installed on the vent fan.
• The scrubbers are all designed to be operated with exhaust silencers. The silencer(s) are shipped separately
and should be installed on the exhaust collars of the blower housing using self tapping screws.