JR-C / JR20-C
KOSMOS SERIE
www.ditel.es
8
Connections
Basic instrument has two rear connectors
CN1
and
CN2
. If 2RE
output option card is installed, two more connectors
CN3
and
CN4
appear. See all four connectors location and their pin out in
the right figure. All female provided terminal connectors are of
CAGE CLAMP
®
technology.
Terminals for
CN2
connector admit cables with section from
0.2mm² up to 1.5mm² (AWG 24÷14).
Terminals for
CN1
,
CN3
and
CN4
connectors admit cables with
section from 0.08mm² up to 2.5mm² (AWG 28÷12).
To perform wiring connections, strip the cable leaving from 7 to
10mm exposed to air, insert it in the proper terminal while
pushing down the key insertion tool to open the clip inside the
connector. Release the key tool to fix wire to the terminal.
Proceed in the same way for the rest of terminals. Once all
connections are done, plug connectors to the instrument.
Rear connectors location.
Key tool for cable insertion.
Notes:
NO
: Normally open contact.
CM
: Common contact.
NC
: Normally closed contact.
*
Polarity in CN1 is indistinct for DC power.
CN3
1 2
CN2
1 2 3 4 5 6 7
CN1
CN4
1
2
3
4
5
6
CN3
(relay 1)
1
NO
2
CM
3
NC
CN4
(relay 2)
4
NO
5
CM
6
NC
WARNING
Isolation
:
1500Vrms for 1 minute to signal terminals (CN2) and power terminals (CN1).
2500Vrms for 1 minute to signal terminals (CN2) and relays terminals (CN3 y CN4).
2500Vrms for 1 minute to power terminals (CN1) and relays terminals (CN3 y CN4).
CN2
1
-IN (COMMON)
2
+IN (300mV / 30mV)
3
N.C.
4
+TARE
5
- EXC / TARE
6
+EXC
7
N.C.
CN1*
1
Phase (AC)
2
Neutral (AC)
Load cell input signal wiring diagrams (mV)
LOAD CELL CONNECTION WITH EXCITATION SUPPLIED BY THE INDICATOR
INDICATOR
LOAD CELL
1
+OUT -OUT
+IN
-IN
±30mV
±300mV
5
2
6
-IN (COMMON)
+IN
+EXC.
-EXC.
NOTE:
The instrument can supply excitation to multiple load cells
connected in parallel as long as 30mA of total load current is
not exceeded.