JR-C / JR20-C
KOSMOS SERIE
www.ditel.es
15
TARE, MAX/MIN and RESET functions
AVAILABLE KEYBOARD FUNCTIONS
Direct access to setpoints value
Pro
SEt1
00.00
SEt2
00.00
FIRST SETPOINT VALUE:
SEt1
:
Setpoint 1 value indication.
00.00
: Value entering in counts within available model display range.
SECOND SETPOINT VALUE:
SEt2
:
Setpoint 2 value indication.
00.00
: Value entering in counts within available model display range.
In addition to already known functions used to browse through the configuration menus and submenus, introduce
and/or modify existing values and parameters, the instrument provides some more added functions.
If 2RE output option is installed, it is possible to access to setpoints value
configuration without having to enter main menu.
To access this submenu, from
RUN
mode and after
ENTER
key is pressed, simply
press
UP
key while “
Pro
” is displayed.
TARE
function activates by pressing
UP
key (or by closing contact between pin 4 and pin 5 from CN2 input
connector, see page 9). Current display value is then stored (or added) in memory and the instrument shows (by
default) "
0.00
" or "
0.0
", depending on whether configured input range is 30mV or 300mV respectively. At the
same time, after the first digit (from the right), a point starts flashing indicating that the instrument has stored a
TARE value.
It is possible to tare instrument as many times as needed, as long as the accumulated value does not exceed the
limit value defined by the working range. Otherwise overflow indication "
OuE
" will be displayed. Stored tare value
remains in memory although power supply is removed.
This device detects and stores in memory maximum and minimum values reached by the input signal. This values
remain in memory although power supply is removed, as well. When pressing repeatedly
SHIFT
key,
MAX/MIN
function shows saved maximum and minimum values in display since last
RESET
function activation.
In order to differentiate this values indication from a mode
RUN
indication, decimal point blinks during the time
these values are showed. The unit automatically switches back to
RUN
mode after 15 seconds have elapsed since
the last key press.
First
SHIFT
key pressing shows “
MAH
” in display followed by the maximum value, a second pressing now shows
“
Min
” followed by the minimum value and finally, a third pressing shows “
run
” to back again in an instant to
RUN
mode.
MAX/MIN RESET
function activates when visualizing maximum or minimum values
SHIFT
key is pressed for at
least 5 seconds. If maximum is the displayed value, current input signal value will replace the previous maximum
saved value. In the same way, current input signal will replace saved minimum value while is the minimum the
displayed value.
TARE RESET
function activates by pressing
UP
key or maintaining remote contact closed for at least 3 seconds.
This is only possible in
RUN
mode. After that time, stored value will be added to the current display and erased
from memory and the flashing point will disappear.