Wiring Details
Communications Wiring
EC-BOS-6
AX
Mounting and Wiring Instructions
Part Number: 05DI-HIBS6AX-10
Revised: February 2008
15
Note
Prior to connecting cables, provide strain relief for them to prevent damage to the controller.
Figure 5
EC-BOS-6
AX
bottom side (cover removed).
Ethernet
Two, female 10/100-Mbit Ethernet connections are provided on the EC-BOS-6
AX
. These are RJ-45 connectors
labeled LAN2 and LAN1. Use a standard Ethernet patch cable for connecting to a hub or Ethernet switch. An
activity LED for each Ethernet port is visible, and are labeled “LAN2” and “LAN1” on the cover.
The factory-default IP address for LAN1 on an EC-BOS-6
AX
is
192.168.1.12n
, where the last numeral
n
in the
address matches the EC-BOS-6
AX
’s serial number, and subnet mask is
255.255.255.0
. By default, LAN2 on an
EC-BOS-6
AX
is disabled. Refer to the
EC-BOS
AX
Install and Startup Guide
for details on changing IP address.
Note
Typically, you
only use LAN1
(primary port), unless you have a specific application for isolating a
driver’s network traffic to a separate LAN, using LAN2. Do
not
use LAN2 as the primary port.
Serial
There are two serial ports on the EC-BOS-6
AX
base unit. Each has a UART capable of operation up to 115,200
baud. At the bottom of the board (see
), the left port is an
port using an DB-9 plug (male)
connector. To the right of this is a two-wire with shield, isolated
port, using a screw-terminal connector
plug.
Note
A green “receive” LED and yellow “transmit” LED are provided for each serial port. These LEDs are
located on the bottom board, on the
opposite side
of the serial connectors (see
These LEDs are labeled on the board (COM1, COM2) and are not visible with the cover on.
RS-232—
An RS-232 serial port using a male DB-9 connector always operates as COM1. You can use standard
DB-9 serial cables with this port. The EC-BOS-6
AX
is a serial DTE device, such another DTE device (PC, for
example) requires a “null modem” cable. If connecting the EC-BOS-6
AX
to a DCE device (modem, for
example), a straight-through cable is used.
provides standard serial DB-9 pinouts.
Battery in bracket
(on top of option
cards, if any)
EC-BOS
AX
Battery
20 Pin Connector
(Power Modules)
Ethernet (RJ-45)
LAN 2
RS-232
(DB-9)
COM1
Primary
Ethernet (RJ-45)
LAN 1
RS-485
(3-pos.)
COM2
Earth Ground
Spade Lug
Barrel power
connector for
EC-WPM-XX
Option Slot area
(Slot #1 this side)
s + –
Содержание EC-BOS-6AX