Power Up and Initial Checkout
Connect the Backup Battery
EC-BOS-6
AX
Mounting and Wiring Instructions
Part Number: 05DI-HIBS6AX-10
Revised: February 2008
17
Connect the Backup Battery
With the cover removed from the EC-BOS-6
AX
(see
“Removing and Replacing the Cover,”
page 7), locate the
red and black wires coming from the backup battery, with 2-position connector plug. Insert the plug into the
battery connector on the bottom board (below option slot 2 area), as shown in
.
Figure 6
Backup battery connector on EC-BOS-6
AX
bottom board.
The connector is keyed—you cannot insert it incorrectly. The red (positive) connection should be the furthest
from the two 30-pin option board connectors. For more battery details, see
Apply Power
Apply power to the EC-BOS-6
AX
by plugging in the power plug into either the EC-BOS-6
AX
(if wall mount AC
adapter EC-WPM-XX) or the 24V-powered EC-NPB-PWR module. If powering using the line-voltage input
EC-NPB-PWR-UN power supply module, energize the 90-263Vac circuit wired to the EC-NPB-PWR-UN
module.
Caution
Do not connect
both
the EC-WPM-
XX
and EC-NPB-PWR/EC-NPB-PWR-UN supplies at the same
time, or equipment damage may result, or a power outage may go unrecognized.
Check the Status LEDs
When power is applied, the green LED labeled “STATUS” will light. This indicates that the system is OK and
that power is applied. Once the EC-BOS-6
AX
boots, the yellow “BEAT” (heartbeat) LED will begin blinking,
with a typical rate of about 1 Hz. Blinking should begin within 30 seconds after power is applied.
If after applying power, the STATUS LED goes out, or if the BEAT LED comes on (steady) and stays lit longer
than two minutes, contact Systems Engineering for technical assistance. See also the
Battery
Connector
Battery
Assembly