background image

4 / 16

Supported Quantity

The  Allure  EC-Smart  Vue  sensor  connects  to  the  controller’s  Subnet  Port.  Other  expansion  modules  may  also  be  connected  to  this  port  in  a  daisy-
chained fashion (see the controller’s datasheet for compatibility information and supported quantities).

Each  controller  supports  a  maximum  number  of  Allure  EC-Smart  Vue  sensors.  The  Subnet  ID  of  all  Allure  EC-Smart  Vue  sensors  must  be  set  to  be
within the shown addressing range.

Series

Maximum Number of Allure EC‑Smart‑Vue sensors

1

Permitted Subnet ID Addressing
Range

ECB‑VAV

ECL‑VAV

ECY-VAV

ECY-VAV-PoE

ECY-303

Up to 4

2

1 to 4

ECB-VAV-O

ECL-VAV-O

ECB-VAVS

ECL-VAVS

ECB-VVTS

ECL-VVTS

ECB-VAV-N

ECL-VAV-N

ECB‑PTU Series

ECL‑PTU Series

ECB‑103

ECL‑103

ECB‑203

ECL‑203

ECY-TU/PTU

4

1 to 4

ECB‑300

ECL‑300

ECB‑400 Series

ECL‑400 Series

ECB‑600 Series

ECL‑600 Series

ECY-S1000 Series

12

1 to 12

Table 1: Number of Allure EC-Smart-Vue sensors supported by controller model

1.

A controller can support a maximum of two (2) Allure EC-Smart Vue sensor models equipped with a CO

2

 sensor. Any remaining connected Allure EC-Smart Vue sensor models must be without a

CO

2

 sensor.

2.

See  the  room  device  calculator  spreadsheet  available  for  download  from  our  website  to  know  the  permitted  quantities  according  to  the  controller  model:  VAV  Smart  Room  Control  Device

Calculator.xlsm.

About the Subnetwork Bus

The ECB-600 and ECL-600 controllers use the Subnetwork bus to support the ECx-400 Series I/O Extension Modules through the controllers 
and Subnet- terminals with 2-wire shielded cable.

The ECB-600 and ECL-600 controllers also use the Subnetwork bus to support one or more Allure Series(s) using standard structural (Cat 5e) cabling.

Содержание Allure EC-Smart-Vue Series

Страница 1: ...Allow for proper clearance around the device s enclosure and wiring terminals to provide easy access for hardware configuration and maintenance Orient the device with the ventilation slots towards the...

Страница 2: ...Mounting pg 3 2 Open the device by pressing in the two 2 tabs on the bottom of the device and pulling the bottom side of the front plate out 3 Set any jumpers see Connector and Jumper Location Identif...

Страница 3: ...Smart Vue Sensor Equipped with a CO Sensor The Allure EC Smart Vue C CM CH CHM sensors are factory calibrated to accurately read CO2 concentration levels at sea level When these Allure EC Smart Vue se...

Страница 4: ...U 4 1 to 4 ECB 300 ECL 300 ECB 400 Series ECL 400 Series ECB 600 Series ECL 600 Series ECY S1000 Series 12 1 to 12 Table 1 Number of Allure EC Smart Vue sensors supported by controller model 1 A contr...

Страница 5: ...ECx 400 Series Subnetwork Bus A controller can support a maximum of two Allure EC Smart Vue sensor models equipped with a CO2 sensor the remaining connected models must be without a CO2 sensor See Tab...

Страница 6: ...us ON EOL OFF Controller Series ECB VAV O ECB VAVS ECB VVTS ECB VAV N ECB 103 ECB 203 Series ECB 300 Series ECB 400 Series Back of Allure EC Smart Vue ECL VAV O ECL VAVS ECL VVTS ECL VAV N ECL 103 ECL...

Страница 7: ...OFF ON EOL OFF EOL ON Typical Compatible Controller I O Extension Modules ECx 4xx ECx 4xx I O Extension Modules 2 Wire Shielded Last daisy chained I O Extension Module EOL Jumper is ON All other I O E...

Страница 8: ...the GEN CFG menu appears on the display OR Screen Timeout 30 seconds 5 Press the down button once to enter the GEN CFG submenu 6 Press the Menu button several times until SUBNET ID appears on the disp...

Страница 9: ...lay OR Screen Timeout 15 seconds 3 Use the down button to set the number to 9995 this is the default password OR Screen Timeout 15 seconds 4 Press the Menu button to submit the password Upon submittin...

Страница 10: ...r s BAUD rate as follows 1 Connect an Allure EC Smart Vue Series Communicating Sensor sensor to the controller with a Cat 5e patch cable Wait for the display to show the room temperature 2 Press and h...

Страница 11: ...rt Vue sensor equipped with a motion sensor to the controller with a Cat 5e patch cable 2 After a 30 second warm up period if movement is detected the motion sensor light will turn on 3 To test the se...

Страница 12: ...the indicator PIR LED jumper is enabled If you wish to disable it set jumper J18 to Disabled See Connector and Jumper Location Identification and Configuration pg 3 BACnet Network Access from the Sens...

Страница 13: ...work segment should have their Net to Subnet Port Settings jumpers enabled Enabling too many Allure EC Smart Vue sensors with network access may cause network communication issues If there are any net...

Страница 14: ...bled Figure 16 LONWORKS Network Bus Topology To temporarily access the LONWORKS LAN for commissioning and maintenance purposes connect a LONWORKS USB network interface to the audio plug port located o...

Страница 15: ...ve Allure EC Smart Vue sensor firmware that supports the motion sensor When the Allure EC Smart Vue sensor is connected to a controller its firmware is loaded from the controller In this case the cont...

Страница 16: ...sible for using the correct wiring procedures and maintaining safe working conditions with fail safe environ ments Distech Controls reserves the right to change delete or add to the information in thi...

Отзывы: