Subnetwork Bus Total Length

The  total  maximum  length  of  all  Subnetwork  buses,  including  both  the  length  of  the  Allure  Series  Communicating  Sensor  Subnetwork  bus  and  the
ECx-400 Series Subnetwork bus is 300 m (1 000 ft). The maximum length of the Allure Series Communicating Sensor Subnetwork bus is 200 m (650 ft).
The maximum length of the ECx-400 Series Subnetwork bus is 300 m (1 000 ft).

Sub-Network Bus Total Length: 300 m (1 000 ft) Maximum

Sub-Network Bus: 200 m

(650 ft) Maximum

Allure EC-Smart-Vue

Sub-Network Bus: 300 m

(1 000 ft) Maximum

ECx-400

Typical Compatible

Controller

Extension I/O Modules

ECx-400

Sub-Network Bus - Cat 5e Cable

with RJ-45 Connectors

Allure EC-Smart-Vue

Sub-Network Bus

ECx-400

2-Wire Shielded Cable

Figure 5:  Subnetwork Bus Overview Showing the Allure EC-Smart-Vue Subnetwork Bus and the ECx-400 Series Subnetwork Bus.

A controller can support a maximum of two Allure EC-Smart-Vue sensor models equipped with a CO

2

 sensor; the remaining connected models must be

without a CO

2

 sensor. See Table 1 for the quantity of room devices supported by each controller model.

For instance, if the controller model supports a subnetwork with 12 Allure EC-Smart-Vue sensors in total, then 10 sensor models must be without a CO2
sensor and the other two can be equipped with a CO2 sensor. To ensure proper operation, it is recommended to distribute the sensors throughout the
length of the subnetwork.

Cat 5e Cable with RJ-45 Connectors

Sub-Network Bus Total Length: 1 000 ft (300 m) Maximum

10x...

2x...

Bus: 600 ft (180 m) Maximum 

Allure EC-Smart-Vue

Sensor Sub-network

ECB-600

ECL-600

or

Typical

Controller

ECx-400

Sub-Network Bus

Figure 6:  Allure EC-Smart-Vue Sensor Subnetwork Length and Distribution

For ECB/ECL-PTU Series controllers, the maximum length between two consecutive devices on the sub-network bus
is 100 feet (30 m).

Содержание Allure EC-Smart-Vue Series

Страница 1: ...Allow for proper clearance around the device s enclosure and wiring terminals to provide easy access for hardware configuration and maintenance Orient the device with the ventilation slots towards the...

Страница 2: ...Mounting pg 3 2 Open the device by pressing in the two 2 tabs on the bottom of the device and pulling the bottom side of the front plate out 3 Set any jumpers see Connector and Jumper Location Identif...

Страница 3: ...Smart Vue Sensor Equipped with a CO Sensor The Allure EC Smart Vue C CM CH CHM sensors are factory calibrated to accurately read CO2 concentration levels at sea level When these Allure EC Smart Vue se...

Страница 4: ...U 4 1 to 4 ECB 300 ECL 300 ECB 400 Series ECL 400 Series ECB 600 Series ECL 600 Series ECY S1000 Series 12 1 to 12 Table 1 Number of Allure EC Smart Vue sensors supported by controller model 1 A contr...

Страница 5: ...ECx 400 Series Subnetwork Bus A controller can support a maximum of two Allure EC Smart Vue sensor models equipped with a CO2 sensor the remaining connected models must be without a CO2 sensor See Tab...

Страница 6: ...us ON EOL OFF Controller Series ECB VAV O ECB VAVS ECB VVTS ECB VAV N ECB 103 ECB 203 Series ECB 300 Series ECB 400 Series Back of Allure EC Smart Vue ECL VAV O ECL VAVS ECL VVTS ECL VAV N ECL 103 ECL...

Страница 7: ...OFF ON EOL OFF EOL ON Typical Compatible Controller I O Extension Modules ECx 4xx ECx 4xx I O Extension Modules 2 Wire Shielded Last daisy chained I O Extension Module EOL Jumper is ON All other I O E...

Страница 8: ...the GEN CFG menu appears on the display OR Screen Timeout 30 seconds 5 Press the down button once to enter the GEN CFG submenu 6 Press the Menu button several times until SUBNET ID appears on the disp...

Страница 9: ...lay OR Screen Timeout 15 seconds 3 Use the down button to set the number to 9995 this is the default password OR Screen Timeout 15 seconds 4 Press the Menu button to submit the password Upon submittin...

Страница 10: ...r s BAUD rate as follows 1 Connect an Allure EC Smart Vue Series Communicating Sensor sensor to the controller with a Cat 5e patch cable Wait for the display to show the room temperature 2 Press and h...

Страница 11: ...rt Vue sensor equipped with a motion sensor to the controller with a Cat 5e patch cable 2 After a 30 second warm up period if movement is detected the motion sensor light will turn on 3 To test the se...

Страница 12: ...the indicator PIR LED jumper is enabled If you wish to disable it set jumper J18 to Disabled See Connector and Jumper Location Identification and Configuration pg 3 BACnet Network Access from the Sens...

Страница 13: ...work segment should have their Net to Subnet Port Settings jumpers enabled Enabling too many Allure EC Smart Vue sensors with network access may cause network communication issues If there are any net...

Страница 14: ...bled Figure 16 LONWORKS Network Bus Topology To temporarily access the LONWORKS LAN for commissioning and maintenance purposes connect a LONWORKS USB network interface to the audio plug port located o...

Страница 15: ...ve Allure EC Smart Vue sensor firmware that supports the motion sensor When the Allure EC Smart Vue sensor is connected to a controller its firmware is loaded from the controller In this case the cont...

Страница 16: ...sible for using the correct wiring procedures and maintaining safe working conditions with fail safe environ ments Distech Controls reserves the right to change delete or add to the information in thi...

Отзывы: