Set the LAN Type

Set the BAC/LON jumper for the type LAN in use: BAC for a BACnet network, LON for a L

ON

W

ORKS

 network.

BAC

LON

3.5 mm (1/8

”) Network 

Access Jack

Network Type 

Jumper

Figure 11:  BAC/LON Jumper Set to the BAC (BACnet) Position when used with ECBSeries Controllers

BAC

LON

3.5 mm (1/8

”) Network 

Access Jack

Network Type 

Jumper

Figure 12:  BAC/LON Jumper: Set to the LON (L

ON

W

ORKS

) Position when used with ECL Series Controllers

Setting Up an Allure EC-Smart-Vue Sensor Equipped with a Motion Sensor

The following procedure describes how to commission and test an Allure EC-Smart-Vue sensor equipped with a motion sensor as well as adjust the mo-
tion sensitivity (Allure EC-Smart-Vue M/-CM/-HM/-CHM sensors).

1. Connect an Allure EC-Smart-Vue sensor equipped with a motion sensor to the controller with a Cat 5e patch cable.
2. After a 30-second warm-up period, if movement is detected, the motion sensor light will turn on.
3. To test the sensor functionality, aim the sensor in the direction you want to detect motion and walk at a normal pace across the typical detection zone

and verify that the sensor light turns on. The light will turn on and after 2 seconds of non-movement, the motion sensor light will turn off.

4.  Now  to  set  the  motion  sensitivity,  on  the  Allure  EC-Smart-Vue  sensor,  press  and  hold  the  Menu  button 

  for  5  seconds  to  enter  the  password

menu. 10000 is shown on the display.

OR

Screen Timeout: 15 seconds

5. Press the down button 

 to set the number to 9995 (this is the default password).

OR

Screen Timeout: 15 seconds

6. Press the Menu button 

 to submit the password. Upon submitting the password, the GEN CFG menu appears on the display.

OR

Screen Timeout: 30 seconds

Содержание Allure EC-Smart-Vue Series

Страница 1: ...Allow for proper clearance around the device s enclosure and wiring terminals to provide easy access for hardware configuration and maintenance Orient the device with the ventilation slots towards the...

Страница 2: ...Mounting pg 3 2 Open the device by pressing in the two 2 tabs on the bottom of the device and pulling the bottom side of the front plate out 3 Set any jumpers see Connector and Jumper Location Identif...

Страница 3: ...Smart Vue Sensor Equipped with a CO Sensor The Allure EC Smart Vue C CM CH CHM sensors are factory calibrated to accurately read CO2 concentration levels at sea level When these Allure EC Smart Vue se...

Страница 4: ...U 4 1 to 4 ECB 300 ECL 300 ECB 400 Series ECL 400 Series ECB 600 Series ECL 600 Series ECY S1000 Series 12 1 to 12 Table 1 Number of Allure EC Smart Vue sensors supported by controller model 1 A contr...

Страница 5: ...ECx 400 Series Subnetwork Bus A controller can support a maximum of two Allure EC Smart Vue sensor models equipped with a CO2 sensor the remaining connected models must be without a CO2 sensor See Tab...

Страница 6: ...us ON EOL OFF Controller Series ECB VAV O ECB VAVS ECB VVTS ECB VAV N ECB 103 ECB 203 Series ECB 300 Series ECB 400 Series Back of Allure EC Smart Vue ECL VAV O ECL VAVS ECL VVTS ECL VAV N ECL 103 ECL...

Страница 7: ...OFF ON EOL OFF EOL ON Typical Compatible Controller I O Extension Modules ECx 4xx ECx 4xx I O Extension Modules 2 Wire Shielded Last daisy chained I O Extension Module EOL Jumper is ON All other I O E...

Страница 8: ...the GEN CFG menu appears on the display OR Screen Timeout 30 seconds 5 Press the down button once to enter the GEN CFG submenu 6 Press the Menu button several times until SUBNET ID appears on the disp...

Страница 9: ...lay OR Screen Timeout 15 seconds 3 Use the down button to set the number to 9995 this is the default password OR Screen Timeout 15 seconds 4 Press the Menu button to submit the password Upon submittin...

Страница 10: ...r s BAUD rate as follows 1 Connect an Allure EC Smart Vue Series Communicating Sensor sensor to the controller with a Cat 5e patch cable Wait for the display to show the room temperature 2 Press and h...

Страница 11: ...rt Vue sensor equipped with a motion sensor to the controller with a Cat 5e patch cable 2 After a 30 second warm up period if movement is detected the motion sensor light will turn on 3 To test the se...

Страница 12: ...the indicator PIR LED jumper is enabled If you wish to disable it set jumper J18 to Disabled See Connector and Jumper Location Identification and Configuration pg 3 BACnet Network Access from the Sens...

Страница 13: ...work segment should have their Net to Subnet Port Settings jumpers enabled Enabling too many Allure EC Smart Vue sensors with network access may cause network communication issues If there are any net...

Страница 14: ...bled Figure 16 LONWORKS Network Bus Topology To temporarily access the LONWORKS LAN for commissioning and maintenance purposes connect a LONWORKS USB network interface to the audio plug port located o...

Страница 15: ...ve Allure EC Smart Vue sensor firmware that supports the motion sensor When the Allure EC Smart Vue sensor is connected to a controller its firmware is loaded from the controller In this case the cont...

Страница 16: ...sible for using the correct wiring procedures and maintaining safe working conditions with fail safe environ ments Distech Controls reserves the right to change delete or add to the information in thi...

Отзывы: