background image

7

Exhaust Air Ducting

The stale air exhaust system is used to draw air from the points in the house where the worst air quality problems
occur.  Due to its lower capacity, the PHRV96 is designed to vent from a single source point only and to the bath-
room that is closest to the unit or directly out of the furnace return. Additional source points may be drained from if
designed properly or installed on a separate Fantech fan bath kit to ventilate additional areas. Fantech bath kits are
listed below and are ideal for both new construction and retro fit.

Fantech bathroom kits for supplemental exhaust:

• REG100 (L/FL)

100cfm per fan

• REG140

190cfm per fan

• DLX110

150cfm per fan

• DLX150 (L/FL)

230cfm per fan

• DLX200

360cfm per fan

PRACTICAL TIPS

INSTALLING DUCTS TO / FROM INSIDE

• Building Codes and Combustion

Appliance Installation Codes do not
allow location of return air grilles or
any opening such as a “breathing tee”
in an enclosed room with spillage sus-
ceptible combustion appliances.

• The fresh air inlet from the HRV needs

to respect a minimum 
distance from the furnace return drop
to ensure proper air mixing and tem-
perature at the furnace core. See fur-
nace manufacturer for appropriate
specifications.

To maximize airflow in the ductwork system, all ducts should be kept short and have as few bends or elbows as possible.  Forty-five degree are preferred to 90º
elbows.  Use “Y” tees instead of 90º elbows whenever possible.
All duct joints must be fastened with screws or duct sealant and wrapped with a quality tape to prevent leakage.  Aluminum foil duct tape is recommended.
Galvanized ducting from the HRV/ERV to the living areas in the house is recommended whenever possible, although flexible duct can be used in moderation when
necessary.

Warning:

The PHRV96 should be installed with a 4” (100mm) duct system that has less than 80 ft (25m) of equivalent duct length on the supply and on the

exhaust side. If longer runs are required, increasing the duct diameter or following the instructions below might help.
It is the responsibility of the installer to ensure all ductwork is sized and installed as designed to ensure the system will perform as intended.  All air movement
devices have a performance curve.  The amount of air (CFM) that an HRV will deliver is directly related to the total external static pressure (E.S.P.) of the sys-
tem.  Static pressure is a measure of resistance imposed on the blower by length of duct work/number of fittings used in duct work, duct heater etc.

SUPPLY AIR DUCTING

In homes without a forced air furnace, fresh air should be supplied to all habitable rooms including, bedrooms and living areas.  It should be supplied from high
wall or ceiling locations.  Grilles that diffuse the air comfortably such as Fantech Contour Grilles are recommended.To avoid possible noise transfer through the
ductwork system, a short length (approximately 12”, 300 mm) of nonmetallic flexible insulated duct should be connected between the HRV and the supply/exhaust
ductwork system.
If the floor is the only option available, then special care should be taken in locating grilles.  Areas such as under baseboard heaters will help to temper the air.
Also optional inline duct heaters are available for mounting in the supply duct work to add heat if required.In homes with a forced air furnace, you may want to
connect the HRV to the furnace ductwork (see information below).

Содержание PHRV

Страница 1: ...PHRV Heat Recovery Ventilator INSTALLATION OPERATION AND MAINTENANCE MANUAL ...

Страница 2: ...des in effect in his area The warranty is limited to 5 years on parts and 7 years on the motor from the date of purchase including parts replaced during this time period If there is no proof of purchase available the date associated with the serial number will be used for the beginning of the warranty period This warranty is the exclusive and only warranty in effect relative to the ventilation sys...

Страница 3: ...d ebm motors with backward curved blades Motors come with permanently lubricated sealed ball bearings to guarantee long life and maintenance free operation Seven 7 year warranty Steep fan curves requires no balancing of airflows CORE Aluminum heat recovery core configured for efficient cross flow ventilation Core is 8 5 x 8 5 216 x 216 mm with a 8 205 mm depth Cores are manufactured by Fantech to ...

Страница 4: ...ower cord w 3 prong plug Continuous ventilation mode of supply and exhaust airstreams 10 254mm of clear ance is recommended for removal of core Pa in wg L s cfm L s cfm L s cfm 25 0 1 45 96 47 99 49 104 50 0 2 40 85 41 88 41 88 75 0 3 32 67 33 69 34 72 100 0 4 26 56 27 58 28 58 125 0 5 20 42 20 43 20 43 EXT STATIC PRESSURE NET SUPPLY AIR FLOW GROSS AIR FLOW SUPPLY EXHAUST C F L s cfm Heating 0 32 ...

Страница 5: ...p should be made in the drain line This will prevent odors from being drawn back up into the unit MOUNTING EASY WALL MOUNT LOCATION The HRV must be located in a heated space where it will be possible to conveniently service the unit Typically the HRV would be located in the mechanical room or an area close to the outside wall where the weatherhoods will be mounted If a basement area is not conveni...

Страница 6: ...and not be compressed The outer liner which acts as a vapor bar rier must be completely sealed to outer wall and the HRV using tape and or caulking A good bead of high quality caulking preferably acoustical sealant will seal the inner flexible duct to both the HRV port and the weatherhood prior to clamping To minimize air flow restriction the flexible insulated duct that connects the two outside w...

Страница 7: ...ed ducting from the HRV ERV to the living areas in the house is recommended whenever possible although flexible duct can be used in moderation when necessary Warning The PHRV96 should be installed with a 4 100mm duct system that has less than 80 ft 25m of equivalent duct length on the supply and on the exhaust side If longer runs are required increasing the duct diameter or following the instructi...

Страница 8: ...n may change depending on model Fully Dedicated System suggested for new construction Stale air drawn from key areas of home bathroom kitchen laundry Fresh air supplied to main living areas NOTE PHRV96 should be mounted with its duct connec tions on top or similar ...

Страница 9: ...ent it is being connected to the HRV ERV s airflow should be confirmed on site using the balancing procedure found in the installation manual If a release is required due to the furnace pulling too much air from the HRV ERV special care and attention is needed to its design DIRECT CONNECTION of the SUPPLY AIR STREAM to the FURNACE COLD AIR RETURN Stale air drawn from key areas of home Building Cod...

Страница 10: ... Air Out damper until you reach the desired velocity Follow the previous steps to adjust the Exhaust Air Out damper if needed B Measure here Measure here 12 300 mm 12 300 mm To avoid airflow turbulence and incorrect readings the airflow velocity should be measured on steel ducting a minimum of 12 300 mm from the unit or elbow and before any transition AIRFLOW STATION GRID METHOD Fantech s superior...

Страница 11: ... Every 3 6 Months Unplug unit before doing any repairs or maintenance a Open access door b Carefully grip handle of core and pull out Core will slide out of the channel c Once removed from the cabinet remove filters d Wash core in warm soapy water do not use dishwasher e Install clean core by a First mounting the bottom flange of the core guide into the bottom channel approximately 1 4 6mm b Mount...

Страница 12: ...control board which offers a wide variety of features making it the ultimate ventilation control system Powrmatic engineers have used the latest technology to provide solid trouble free operation under any conditions The Powrmatic uni control board offers stand alone operating capabilities as well as an exclusive 2 wire communication to most external controls The trouble free optional controls inc...

Страница 13: ...he control when needed PRACTICAL TIPS All controls are low voltage 18 to 24 gauge wire is recommended OPTIONAL REMOTE CONTROLS OPERATION CONT D NOTE A dehumidistat is ideal for use in energy efficient houses where indoor humidity during the heating season is higher than outdoor levels High humidity is a major cause of structure damage and IAQ problems such as mold and mildew 2 wire installation 4 ...

Страница 14: ...RV Locate the grilles high on the walls or under the baseboards install ceiling mounted diffuser or grilles so as not to directly spill the supply air on the occupant eg Over a sofa Turn down the HRV supply speed A small duct heater 1kw could be used to temper the supply air Placement of furniture or closed doors is restricting the movement of air in the home If supply air is ducted into furnace r...

Страница 15: ...timer up to 5 timers Dehumidistat 2 wires Dehumidistat On Off 4 wires Mechanical Crank Timer 2 wires and or and or 1 only Air Quality Sensor CUR SW DEHUM N C N O TIMER EDF COM FURNACE INTERLOCK IN COM EDF5 or EDF2 not shown EDF1 RTS3 observe plarity Wiring diagram of complete unit inside of access panel 2 wires 2 wires 3 wires ...

Страница 16: ... the furnace has the effect of energizing Y at the thermostat and thereby turning on the cooling system If you identify this type of thermostat you must use the Alternate Furnace Interlock Wiring PRACTICAL TIPS ELECTRICAL CONNEC TION TO A FURNACE Standard Accessory Control Contact Alternate Accessory Control Contact Item 403322 Rev Date 030806 Montréal 9500 BLVD Ray Lawson Anjou QC H1J 1L1 T 514 4...

Отзывы: