background image

Instructions for Use 

 

Dipl.-Ing. H. Horstmann GmbH 

SMART NAVIGATOR 

 

15 

P

ART 

4

 

-

 

T

ECHNICAL 

D

ATA

 

 

TECHNICAL DATA 

Electricial Data:

 

  Corresponding to ANSI / IEEE Std 495-2007 

Trip current (unleveled) 

  50 A - 1200 A / 200 ms  

Local indication / Flashing frequency  

Super bright red LED / 30 per minute 

Current reading range 

3 A to 10 kA 

Load tracking  

Initiated with load current 

 20 A 

Temperature range  

-30 up to +70 °C (ANSI test -40 up to +85 °C passed) 

Trip Current Accuracy  

±10 % @100 A @ 20 °C 

Trip factor  

4 times load current @ 200ms 

Level delay  

60 sec.  

Level memory  

72 hours  

Function test / reset  

by use of permanent magnet 

Automatic time reset  

4 hours 

Current reset  

 3 A 

Power source  

1 Lithium - Battery, replaceable, 15 years shelf life 

Maximum operating voltage / Frequency  

46 kV / 60Hz 

Current withstand  

25 kA / 1s 

 

 

 

Transmitter Part: 

 

Frequency / Power / Modulation  

2.4 GHz / 1 mW / 2-FSK 

Range  

> 100 ft. (30 m) installed on overhead 

Distinction of different units  

Up to 12 addressable units 

 

 

Mechanical Data:

 

 

Cable diameter range  

0,31-1,15“ (8-29mm) 

Housing material  

PA / PC; UV stable 

Current transformer  

Closed core 

Weight  

420 g 

EMI  

IEC 1000-4-2 (ESD), IEC 1000-4-3 (HF) 

 

 

Catalog No.: 

 

43-xxxx-xxx 

 

Содержание SMART NAVIGATOR

Страница 1: ...Dipl Ing H Horstmann GmbH Humboldtstra e 2 42579 Heiligenhaus www horstmanngmbh com Instructions for Use SMART NAVIGATOR 14 September 2010...

Страница 2: ...ation and Reset 8 2 2 3 Fault Indication and Line Monitoring by Radio Signal 9 2 3 Wireless Communication 9 2 3 1 Priority Events communicate by exception 9 2 3 2 Reports communicate by routine interv...

Страница 3: ...ice here _______________________________ You will find all data on the name plate attached to the housing of the instrument The content of this operating manual reflects the current state of the art a...

Страница 4: ...INFORMATION FOR CANADA Warning Installation connection and commissioning of the SMART NAVIGATOR must be carried out exclusively by a skilled qualified electrician observing the applicable safety rule...

Страница 5: ...VIGATOR Part 4 Technical Data Contains the technical data of the Navigator SMART NAVIGATOR 1 2 ABBREVIATIONS Abbreviation Definition DA Distribution Automation FCI Faulted Circuit Indicator ISM Indust...

Страница 6: ...ine section This substantially speeds up the process of restoring the power supply to the utility customers In addition the SMART NAVIGATOR continuously monitors and transmits circuit status informati...

Страница 7: ...Instructions for Use Dipl Ing H Horstmann GmbH SMART NAVIGATOR 7 PART 2 FUNCTIONALITY 2 1 DEVICE DESCRIPTION Figure 2 1 NAVIGATOR 2D View Battery Compartments...

Страница 8: ...The SMART NAVIGATOR features one ultra bright RED LED that provides fault information LED Status Meaning Off Normal status of FCI 1 RED LED Flashing Fault Indication Fault detection is indicated by a...

Страница 9: ...EIVER via low power RF wireless technology using the world wide available 2 4GHz ISM Industrial Scientific Medical frequency band The range between the SMART RECEIVER and a SMART NAVIGATOR can extend...

Страница 10: ...TEST with a magnet for 0 2s does test the local indication and radio link It turns the FCI ON and activates a local fault indication LED flashing The unit will be flashing until reset by magnet elapse...

Страница 11: ...overhead line The field replaceable battery provides operational power Not only dependent on line current or voltage for its power the fault indicator is constantly armed ready to register switching i...

Страница 12: ...Installation should be carried out observing appropriate safety regulations and the use of proper protective equipment such as hot sticks Operators must maintain safe clearance from electrical power...

Страница 13: ...r momentary fault information 3 Low battery Whenever a SMART NAVIGATOR detects that its battery is approaching its end of life it sends the Low Battery information 4 Test FCI ON Activating the reed co...

Страница 14: ...or pairing with a SMART NAVIGATOR Step 3 Hold the magnet close to the RESET point of the SMART NAVIGATOR until a yellow LED in the SMART NAVIGATOR lights up twice If after a maximum of 10 seconds eith...

Страница 15: ...factor 4 times load current 200ms Level delay 60 sec Level memory 72 hours Function test reset by use of permanent magnet Automatic time reset 4 hours Current reset 3 A Power source 1 Lithium Battery...

Страница 16: ...Dipl Ing H Horstmann GmbH Instructions for Use 16 SMART NAVIGATOR 4 1 PRODUCT FOTO LABEL INFORMATION Label with FCC ID IC ID...

Отзывы: