PDU–4xx–W
©
Dinel, s.r.o.
24
•
"timE"
maximum time of displaying of the peak (drop) value, can be set from 0.0 to 19.9 sec, with
0.1 sec.
•
"HdiS"
type of displayed values:
"rEAL"
current value is displayed
"HOLd"
peak (drop) value is displayed
Parameter "bri"
This parameter allows user to set bright of the LED display, bright can be set to conventional values
from 1 to 8.
Menu "HOLd"
The unit is equipped with peak detection function. It is able to detect the peaks in the input signal
and display the values in the display. This is set up in the
”HOLd”
menu. Detection of peak values
is enabled when the measured signal is rising or dropping with regard to the value at least equal
to the
”PEA”
parameter. The detected peak values are shown on display over time, defined by the
”timE”
parameter. If a new peak value is detected, the value is automatically displayed. The time
counter shown in the display is erased. However, if no peak is detected before the
”timE”
expires,
the device once again shows the current values of the input signal.
Relays/LED indicators and current output may be controlled depending on the value of the input
signal current or peak value (see the
”HOLd” menu
).
•
"modE"
the type of detected changes of the input signal, can be set to values:
"norm"
peaks, peak and next drop of the input signal of value equal at least
“PEA”
"inv"
drops, drop and next peak of the input signal of value equal at least
“PEA”
•
"PEA"
minimal detected signal change classified as peak or drop.