Product Information
Safety technics modular generation in metal housing version 08 dated: 2009-04-10 page 8 from 32
Adjusting table DNDS 1EG V7A item-no. 22EG31 and DNDS 1EG V7C item-no. 22EG36
R1 and SH Table:
Selection of the monitoring frequencies via the DIP
switches S3 and S5 for tool setting and semi automatic mode
D-Table
: Selection of the monitoring frequencies for
the automatic mode via the D-inputs
Switch positions
Switch positions
D-Table
: D-inputs connected to 24V DC
Mode3
of S3 and S5
Mode3
of S3 and S5
Selection D1-D6
Selection D1-D6
SH
R1
Position = ON
SH
R1
Position = ON
D D D D D D
D D D D D D
Mode2 Hz
Hz
1 2 3 4 5 6
Mode2
Hz
Hz
1 2 3 4 5 6
1
2
3
4
5
6
Hz
1
2
3
4
5
6
Hz
00
50 125
32
96 600
00
5
32
249
01
240 600
33
70 440
01
30
33
262
02
20
50
34
6,25
20 125
02
35
34
277
03
96 240
35
50 312
03
40
35
292
04
2,5
40 100
36
75 469
04
45
36
308
05
30
75
37
20 140
05
50
37
325
06
125 312
38
7,0
50 350
06
55
38
343
07
200 500
39
75 525
07
60
39
362
08
40
20 155
08
65
40
381
09
41
7,75
50 387
09
70
41
402
10
20
20
42
75 581
10
75
42
425
11
1,0
50
50
43
9,0
20 180
11
80
43
448
12
125 125
44
50 450
12
85
44
473
13
240 240
45
10,0
20 200
13
90
45
499
14
20
40
46
50 500
14
95
46
526
15
2,0
50 100
47
15
100 47
555
16
125 250
48
1,25
240 300
16
105 48
585
17
240 480
49
17
111 49
618
18
20
65
50
1,50
240 360
18
117 50
652
19
3,25
50 162
51
19
124 51
687
20
100 325
52
1,75
240 420
20
131 52
725
21
150 487
53
21
138 53
765
22
20
80
54
22
146 54
807
23
4,0
50 200
55
23
154 55
852
24
100 400
56
24
162 56
900
25
150 600
57
25
171 57
950
26
20
95
58
1,5
14
21
26
180 58
1000
27
4,75
50 237
59
2,4
5
12
27
190 59
1050
28
100 475
60
2,42
7
17
28
201 60
1100
29
20 110
61
2,50
10
25
29
212 61
1150
30
5,5
50 275
62
2,53
15
38
30
223 62
1200
31
100 550
63
31
236 63
1250
Using the modules to monitor the function modes of a machine
Using the M-inputs respectively the MT-input for the not monitored automatic function mode (mode 1)
The M-inputs of DNDS 1EG V7A respectively the MT-input of DNDS 1EG V7C can be used, if the mode 1 has to
be not monitored. If the automatic function mode has to be not monitored, these inputs have to be connected to
24V. These inputs have to be disconnected from 24V, if the automatic function mode or other function modes have
to be monitored. Look to the priority of the inputs.
Using the inputs D1-D6 to monitor the automatic function mode (mode 1)
With the D-inputs 63 different monitoring frequencies for mode 1 can be selected. Mode 1 will be monitored, if one
or more D-inputs are connected to 24V. All D-inputs have to be disconnected from 24V, if other function modes
have to be monitored. See D-Table.
Using the R1-input to monitor the semi automatic function mode (mode 3)
Mode 3 can be monitored, if the R1-input is connected to 24V. For the monitoring of mode 3 the M-inputs of DNDS
1EG V7A respectively the MT-input of DNDS 1EG V7C and the D-inputs have to be disconnected from 24V.
Using the SH-input to monitor the tool setting function mode (mode 2)
Mode 2 can be monitored, if the SH-input is connected to 24V. For the monitoring of mode 2 the M-inputs of DNDS
1EG V7A rather the MT-input of DNDS 1EG V7C, the D-inputs and the R1-input have to be disconnected from
24V.
For the monitoring of the tool setting and the semi automatic function mode there are a lot of monitoring frequen-
cies. These can be selected via the DIP switches S3 and S5. See R1 and SH Table.
Monitoring of the standstill
To monitor the standstill the inputs M11, M12 of V7A respectively the input MT of V7C, the inputs D1-D6, R1- and
SH-input have to be disconnected from 24V.
STOP output of the output modules
The STOP output of all output modules is independent of all function modes. It works autarkic.
DNDS 1EG V7A
Priority of the inputs: M > D
D > R1
R1 > SH
SH > Standstill
DNDS 1EG V7C
Priority of the inputs: MT > D
D > R1
R1 > SH
SH > Standstill