www.gdts.one
452237.66.54 · FD 9912
EN-11
SI 35TUR
English
13 Device information
1
Type and order code
SI 35TUR
2
Design
Heat source
Brine
2.1
Model
Reversible
2.2
Controller
Integrated
2.3
Thermal energy metering
Integrated
2.4
Installation location
Inside
2.5
Performance levels
2
3
Operating limits
3.1
Heating water flow
°C
+20 to +62±2
Cooling water flow
°C
+7
1
/ +9
2
to +20
Brine (heat source, heating)
°C
-5 to +25
Brine (heat sink, cooling)
°C
+10 to +30
Antifreeze
Monoethylene glycol
Minimum brine concentration (-13 °C freezing temperature)
25%
4
Performance data
3
4.1
Heating flow / free compression
Brine
Heating water
Nominal flow in accordance with EN 14511with B0 / W35-30
m³/h / Pa
8.0 / 61200
5.9 / 39900
at B0 / W45-40
m³/h / Pa
7.4 / 71000
5.6 / 44000
at B0 / W55-47
m³/h / Pa
6.7 / 78900
3.3 / 84700
Minimum flow rate
m³/h / Pa
6.7 / 78900
3.3 / 84700
4.2
Heat output / coefficient of performance
4
performance level
1
2
at B-5 / W55
kW / ---
13.3 / 2.7
26.9 / 2.6
at B0 / W55-47
kW / ---
15.3 / 3.0
30.3 / 2.9
at B0 / W45-40
kW / ---
16.8 / 3.9
31.9 / 3.6
at B0 / W35-30
kW / ---
18.4 / 5.1
33.7 / 4.6
4.3
Cooling flow / free compression
Brine
Cooling water
Minimum flow rate
m³/h Pa
8.0 / 61200
5.9 / 39900
4.4
Cooling capacity / coefficient of performance
1
2
at B20 / W9
kW / ---
---
40.1 / 6.0
at B20 / W7
kW / ---
17.3 / 6.1
---
at B20 / W18
kW / ---
22.9 / 7.8
50.6 / 6.9
at B10 / W9
kW / ---
---
42.1 / 7.4
at B10 / W7
kW / ---
17.6 / 7.5
---
at B10 / W18
kW / ---
17.8 / 8.2
44.6 / 9.3
4.5
Sound power level according to EN12102
dB(A)
58
4.6
Sound pressure level at a distance of 1 m
5
dB(A)
42
5
Dimensions, connections and weight
5.1
Device dimensions
6
H x W x L mm
880 x 1000 x 750
5.2
Weight of the transportable unit(s) incl. packaging
kg
305
5.3
Device connections for heating
inches
G 1½“ external thread
5.4
Device connections for heat source
inches
G 1½“ external thread
5.5
Refrigerant / total filling quantity
type / kg
R410A / 8.0
5.6
GWP value / CO2 equivalent
--- / t
2088 / 17
5.7
Refrigeration circuit hermetically sealed
Yes
5.8
Lubricant / total filling quantity
type / litres
Polyolester (POE)/4.4
5.9
Volume of heating water in device
litres
9
5.10 Volume of heat transfer medium in device
litres
9
Содержание SI 35TUR
Страница 2: ......
Страница 30: ...EN 14 452237 66 54 FD 9912 www gdts one English SI 35TUR...
Страница 44: ...FR 14 452237 66 54 FD 9912 www gdts one Fran ais SI 35TUR...
Страница 57: ...www gdts one 452237 66 54 FD 9912 A XIII SI 35TUR Anhang Appendix Annexes...