Dimensions Unlimited
20
5
Indicates that the SPS has shut
off due to an overload
condition.
Remove the short circuit or excessive
load from the output, and then press
the
“inverter & Reset On/Off”
button
three times to turn the inverter back
ON. If the condition persists, call
Dimensions.
6
Indicates that the inverter has
shut off due to high internal
temperature. The unit will
automatically turn back on
when it has cooled to 40°C
(104°F)
Verify that the SPS is not in a closed
compartment and that the fan is not
blocked. High ambient temperatures
combined with a poor ventilation
condition may also contribute to the
shut down of the SPS.
7
Indicates that the inverter has
shut off due to high battery
voltage.
The
unit
will
automatically turn back on
when
the
condition
is
removed.
Check battery wiring or remove
other source of battery charging,
such as the vehicle alternator.
8
Indicates that the charger has
shut off due to high internal
temperature. The unit will
automatically turn back on
when it has cooled to 40°C
(104°F)
Shorted or defective battery. Make
sure that the DC cable connections
are tight and clean and not shorted,
and that the proper wire gauge is
used.
9
Indicates that the charger has
shut off due to high battery
temperature 47°C – 50°C
(117°F - 122°F).
Battery compartment is too hot and
needs to cool down. The charger will
automatically turn back on when it
has cooled down to 40°C (104°F)
10
Indicates that the charger has
shut off due to short or open
temperature
compensating
sensor cable.
Temperature compensation sensor
cable needs to be replaced.
11
Indicates that the charger is
operating in a low DC output
voltage condition.
Shorted or defective battery. Make
sure that the DC cable connections
are tight and clean and not shorted,
and that the proper wire gauge is
used.
12
Indicates that the charger is
operating in a high DC output
voltage condition.
There is another source of battery
charging or there is a defective
battery charger. Disconnect and
reconnect the external AC power to
restart the battery charger. If
condition persists, call Dimensions.
INVERTER - OFF
HIGH TEMP
CHARGER - OFF
HIGH TEMP
CHGR-OFF HI-VOLT
RESET OR SERVICE
CHGR-ON LO-VOLT
CHECK BATTERIES
INVERTER - OFF
HIGH BATTERY
INVERTER - OFF
OVERLOAD
CHARGER - OFF
BATT HIGH TEMP
CHARGER - OFF
CHECK BATT PROBE