4.2. The encoder

The  encoder  is  used  for  getting  the  actual  position,  necessary  for  the  cam  controller.  Only  encoders
with an SSI interface can be connected to CamCon DC33/X. The SSI interface is a common interface
for  absolute  single  and  multiturn  encoders.  The  CamCon  supplies  the  measuring  system  with  24Volt
via this interface. To read the data, CamCon sends a clock signal with an RS422 level to the encoder.
The  encoder  the  answers  synchronously  with  the  output  (data)  of  the  position  in  Gray  code.  The
frequency of the clock signal depends on the length of the cable connecting ecoder and CamCon. The
cable length can be maximum of 200 metre.

Note:

 The data protocol corresponds with the Stegmann SSI Norm.

Tp

= clock impulse

Tmono

= mono flop time 25µs

Attention:

Use  only  a  covered  double  entwired  connection  cable.  The
wiring  should  not  be  near  power  current  lines.  Ground  the
covers at both sides.

4.3. The outputs

CamCon  is  equipped  with  either  8  or  16  short  circuit-proof  outputs,  depending  on  the  version.  They
emmit  24V  high  active  signals  and  are  not  potentially  free.  They  supply  up  to  500mA  permanent
current  in  a  surrounding  temperature  of  25°C.  If  an  output  short  circuits  or  overloads,  the  device
switches off with the 

"A-Err"

 message.

Attention:

 

With  inductive  loads  the  outputs  have  to  be  switched  with  free  wheeling
diodes.

4.4. External program selection

The  CamCon  offers  the  possibility  to  select  the  desired  program  number  externally,  through  special
outputs. To do this you have to enter the program number as a binary digit at the pins for the external
program selection (pins 28, 29 and 30). With an inpulse (+24V), that has to be entered at least 20ms
after the program number and that has to be at least 20ms long, the program is selected at the input
for the program number transfer (pin 31).

4.5. External activation of the keyboard lock

A signal (+24V DC) at the input for the activation of  the  keyboard  lock  (pin  32)  disables  the  keys 

and 

. This makes it impossible to initialize or program the device.

4.6. Precautions to be taken at welding operations

For the duration of welding operations carried out at the machine, the connecting wires concerning the
data  exchange  from  the  measuring  system  to  the  CamCon  and  the  power  supply  as  well  as  the
grounding connections and inputs and outputs have to be separated from the CamCon.

Version from: 18.06.2009

Page: 12

Содержание CamCon DC33/X

Страница 1: ...programs Digitronic Automationsanlagen GmbH Steinbeisstra e 3 D 72636 Frickenhausen Tel 49 7022 40590 0 Fax 10 Auf der Langwies 1 D 65510 H nstetten Wallbach Tel 49 6126 9453 0 Fax 42 Internet http w...

Страница 2: ...ove mentioned limits to liability do not apply to insurance of named characteristics and damages which were caused deliberately or through negligence Protection The CamCon DC33 X and this instruction...

Страница 3: ...on and speed 13 6 Commissioning 14 6 1 Complete deletion 14 6 2 Initialization 14 6 2 1 User keys for the system registers 14 6 2 2 The encoder resolution 15 6 2 3 The F R change over 15 6 2 4 The zer...

Страница 4: ...mode 1 22 6 5 6 1 Cam programming 22 6 5 6 2 Deletion of cams 22 7 Outline of operations 23 7 1 Switching the standard display 23 7 2 Programming the system constants 23 7 3 Dead time programming 23 7...

Страница 5: ...for switch ON and switch OFF points can be set in steps of 100 s separately DTC delay time or Speed Compensation Not linear Speed Compensation NLT Position Triggert Time Cams Power supply 24V DC 20 M...

Страница 6: ...s here presented as three tracks occur when the three cam disks turn anti clockwise past a sensor which scans the cams on the 0 axis In a mechanical cam switch unit the switch interval i e the range b...

Страница 7: ...e nozzle opens for a short time during which a drop of glue ejects Between the start of the impulse and the exit of the drop time passes which is mainly caused by the delay time of the magnetic valve...

Страница 8: ...oves on by the distance x vpaper Ttotal delay 1m s 30ms 30mm In order to compensate the delay time the switch point for the magnetic valve must be moved forward by 30 If the speed of the device and co...

Страница 9: ...oint is calculated at a speed of for example 50 rpm We assume that the programmed switch point lies at 200 in this case The second measurement is taken at a speed of 80 rpm The necessary switch point...

Страница 10: ...to a grounding point of the switchboard door in the shortest possible way All cable connections must be done in a cold state The connection cables e g for the measuring system or the serial interface...

Страница 11: ...4 Pin 12 Output 5 Pin 13 Output 6 Pin 14 Output 7 Pin 15 Output 8 Pin 16 24V DC supply Pin 17 0V supply Pin 18 Output 9 A Pin 19 Output 10 B Pin 20 Output 11 C Pin 21 Output 12 D Pin 22 Output 13 E P...

Страница 12: ...nals and are not potentially free They supply up to 500mA permanent current in a surrounding temperature of 25 C If an output short circuits or overloads the device switches off with the A Err message...

Страница 13: ...ntil released The key is used to reduce the input values by the value one Keeping the key pressed for about two seconds will cause the input values to decrease automatically until the release of the k...

Страница 14: ...Wait until the display shows either a number or 3 Press the key four times 4 Press the key four times 5 Press the key about 2sec until is displayed 6 Press the key about 2sec until the display goes o...

Страница 15: ...of the programming mode appears on the display after you press the key Here you can set the mode for cam programming Pressing either the or the key results in a change over from programming mode 0 to...

Страница 16: ...mode you can search for the cam activation points by pressing the key Every time the key is pressed CamCon searches the memory for activation points of the cams on the corresponding output If no cam h...

Страница 17: ...the following system A single short pressing of the key will set a new switching point at the previously displayed preset value e g 100 Then the preset value is increased by one e g to 101 A short pre...

Страница 18: ...ed until is displayed 7 If you have released the key too early or too late you can adjust the preselection to 100 with the or the key 8 Press the key the activation point is displayed 9 Press the key...

Страница 19: ...ears on the display 7 If you have released the key too early or too late you can adjust the preselection to 300 with the or the key 8 Press the key the activation point is displayed 9 Press the key to...

Страница 20: ...Press the key The preselection is displayed 7 Press the key to program the activation point The display shows 8 Press the key and keep it pressed until the display shows CAUTION Do not keep the key p...

Страница 21: ...essing of the key or the key shifts the activation point by one step This is done according to the following system A short single pressing of the key will erase the activation point at the previously...

Страница 22: ...r the key 7 Press the key to program the deactivation point 8 Press the key and keep it pressed until the display shows 9 If you have released the key too early or too late you can adjust the deactiva...

Страница 23: ...key shortly Encoder F R switching Press the key shortly Zero point correction Press the key shortly Cam programming mode Press the key shortly Display of program and speed display min 1 7 3 Dead time...

Страница 24: ...the input encoder resolution Check the wiring to the encoder or the input of the encoder resolution When the error is corrected press any key to clear the error message of the display Problem The disp...

Страница 25: ...gth of the connecting cable between encoder and CamCon 200m Data security memory EEPROM Supply voltage 24V DC 20 Encoder supply voltage with 24V DC over supply voltage of CamCon Current reception 200m...

Страница 26: ...lay of position and speed 13 Encoder 12 Encoder resolution 15 F R change over 15 Grounding pins 10 Initialization 14 Installation 10 Installation procedures 10 Keyboard 13 Keyboard lock external activ...

Страница 27: ...Switch Unit Automationsanlagen GmbH CamCon DC33 X with 8 programs Table of contents 3 Technical data 25 Troubleshooting 24 Update 2 User keys 14 watch doc 24 Y2K 2 Zero point correction 15 Version fr...

Отзывы: