2.1 Parallel Disk Array Site Preparation
2.1.3 Power and Environmental Specifications
Table 2–1 provides the PDA electrical and environmental specifications.
Table 2–1 PDA Specifications
Item
Specification
Line Voltage
220/240 Vac, 20A, 50/60 Hz, single phase
Line Voltage Tolerance
180 V minimum, 264 V maximum
Maximum Power
2500 W
Operating Temperature
10–40°C (50–104°F)
Humidity
20–80% noncondensing
Maximum Wet Bulb
Temperature
28°C (82°F)
Minimum Dew Point
2°C (36°F)
Maximum Altitude
2400 m (8000 ft) at 36°C (96°F)
Cooling Requirement
8540 Btu/hour (up to 19 disks)
Parallel Disk Array Installation 2–3