- 32 -
5.10 Advanced Func�on Setup Menu
Solar Arc Fault ON
Clear Arc_Fault
System selfcheck
BMS_Err_Stop
0S
2000
:
1
Backup Delay
Advanced Function
Func
Set1
DRM
Gen peak-shaving
CT Ratio
Signal ISLAND MODE
Solar Arc Fault ON:
This is only for US.
System selfcheck:
Disable. this is only for factory.
Gen Peak-shaving:
Enable When the power of the
generator exceeds the rated value of it, the inverter will
provide the redundant part to ensure that the generator
will not overload.
DRM:
For AS4777 standard
Backup Delay:
Reserved
BMS_Err_Stop:
When it is ac�ve, if the ba�ery BMS failed
to communicate with inverter, the inverter will stop
working and report fault.
Signal island mode:
when the inverter connects grid,
the ATS port will output 230Vac and it is used to cuts off
Earth-Neutral(load port N line) bond via connect external
relay. When the inverter disconnects from the grid, ATS
port voltage will be 0 and the Earth-Neutral bond keeps
on. More details, please refer to le� picture.
coil
external relay
closed
contact
L N
ATS
load port
Inverter
shell
Ground cable
230V
Ex_Meter For CT:
when in Three phase system with CHNT
Three phase energy meter (DTSU666), click corresponding
phase where hybrid inverter is connected. e.g. when the
hybrid inverter output connects to A phase, please click A
Phase.
Parallel
Master
Slave
Ex_Meter For CT
C Phase
00
Modbus SN
Advanced Function
Paral.
Set3
A Phase
B Phase
B Phase
A Phase
C Phase
DC1 for WindTurbine
V1
V2
V3
V4
V5
V6
V7
V8
V9
V10
V11
V12
0V
0V
0V
0V
0V
0V
0.0A
0.0A
0.0A
0.0A
0.0A
0.0A
0V
0V
0V
0V
0V
0V
0.0A
0.0A
0.0A
0.0A
0.0A
0.0A
DC2 for WindTurbine
Advanced Function
Wind
Set2
This is for Wind Turbine
Note:
This interface is not available for some firmware
version
Содержание SUN 5K-SG01LP1-US
Страница 1: ...Hybrid Inverter User Manual R ...
Страница 12: ...3 3 2 Ba ery temperature connec on 1 2 Temp CT 10 ...