- 29 -
There are 3 stages of charging the Ba�ery .
①
②
This is for professional installers, you can keep it
if you do not know.
Shutdown 20%:
The inverter will shutdown if the SOC
below this value.
Low Ba� 35%:
The inverter will alarm if the SOC
below this value.
Restart 50%:
Ba�ery SOC at 50% AC output will resume.
③
Float V
53.6V
20%
35%
50%
-5
Absorption V
57.6V
Equalization V
57.6V
Equalization Days
Shutdown
Low Batt
Restart
TEMPCO(mV/C/Cell)
Batt Resistance
30 days
Equalization Hours
3.0
hours
25mOhms
Battery Setting
Set3
Batt
①
②
③
Recommended ba�ery se�ngs
Battery Type
AGM (or PCC)
Absorption Stage
14.2v (57.6v)
13.4v (53.6v)
Float Stage
Torque value
(every 30 days 3hr )
14.2v(57.6v)
Gel
14.1v (56.4v)
13.5v (54.0v)
Wet
14.7v (59.0v)
13.7v (55.0v)
14.7v(59.0v)
Lithium
Follow its BMS voltage parameters