- 09 -
Batt Temp
Sensor
1 2 3 4 5 6 7 8 9 10
RS 485
Meter_CON Parallel_A Parallel_B
CAN
TEMP (1,2): ba�ery temperature sensor for
lead acid ba�ery.
CT-L1 (3,4): current transformer (CT1) for
“zero export to CT”mode clamps
on L1 when in split phase system.
CT-L2 (5,6): current transformer (CT2) for
“zero export to CT”mode clamps
on L2 when in split phase system.
G-start (7,8): dry contact signal for startup
the diesel generator.
When the "GEN signal" is ac�ve, the open
contact (GS) will switch on (no voltage output).
G-valve (9,10): reserved.
RSD (11,12): provide 12Vdc output when
inverter is on.
ATS: 230V output port when inverter is on
Note: For - EU model (7.6/8kW,230V@50Hz),
1pcs CT is needed only, and the secondary
side of the CT should be connected to
5&6 port (CT-L2).
CT -L1
CT -L2
Gen ATS
N/O Relay
Neutral
Earth
Bond
240V Coil
Inverter
11 12
ATS
GS (diesel generator startup signal)
relay
coil
open
contact
G
S
RS 485: RS 485 port for ba�ery
communica�on.
CAN: CAN port for ba�ery
communica�on.
Parallel A: Parallel communica�on port 1
(
CAN interface
).
Parallel B: Parallel communica�on port 2
(
CAN interface
).
Meter_CON: for energy meter
communica�on.