- 49 -
"Q(U)" Mode Parameters Explanation
Start
0%-130% Rate out power
The QU mode starts when the active power
is greater than this value
The QU mode stops when the active power
is less than this value
Grid voltage limit at point (U1,Q1) on the
Q(U) mode curve
Grid voltage limit at point (U2,Q2) on the
Q(U) mode curve
Grid voltage limit at point (U3,Q3) on the
Q(U) mode curve
Grid voltage limit at point (U4,Q4) on the
Q(U) mode curve
Grid voltage limit at point (U5,Q5) on the
Q(U) mode curve
Grid voltage limit at point (U6,Q6) on the
Q(U) mode curve
Value of Q/Pn at point (U1,Q1) on the Q(U)
mode curve
Value of Q/Pn at point (U2,Q2) on the Q(U)
mode curve
Value of Q/Pn at point (U3,Q3) on the Q(U)
mode curve
Value of Q/Pn at point (U4,Q4) on the Q(U)
mode curve
Value of Q/Pn at point (U5,Q5) on the Q(U)
mode curve
Value of Q/Pn at point (U6,Q6) on the Q(U)
mode curve
0%-130% Rate out power
0-110% VRated
-60% -60% Q/Pn
0-110% VRated
-60% -60% Q/Pn
0-110% VRated
-60% -60% Q/Pn
0-110% VRated
-60% -60% Q/Pn
0-110% VRated
-60% -60% Q/Pn
0-110% VRated
-60% -60% Q/Pn
Stop
Q1
Q2
Q3
V1
V2
V3
Q4
V4
Q5
V5
Q6
V6
Increase or decrease the time required for
the reactive power to reach the specified
value of the curve.
0-1000s
RMpTime
Point number used in QU Curve
2-6
PtUsed
QU Curve
Curve
Parameter
Range
Description