- 47 -
When the frequency exceeds
StopPoint
: 51.5Hz, the inverter output should stop (ie 0 W).
When the frequency is lower than
StopPoint
: 51.5 Hz, the inverter will linearly increase the power
output with a gradient of 100% Pmax/Hz un�l it reaches
StopPoint
: 50.5 Hz.
In the hysteresis mode, when the frequency is lower than
StopPoint
: 51.5 Hz, the inverter will not
increase the power output un�l it is lower than
RecoverPoint
: 50.1 Hz.
The inverter provides a reactive power regulation function.
Tap
Reactive Power Regulation Mode
to select proper regulation mode and set the
corresponding parameters.
The reac�ve power regula�on func�on is disabled. The PF is fixed at +1.000
"OFF" Mode
Adjust reac�ve power output in %.
ReactiveP
The power factor (PF) is fixed and the reac�ve power is regulated by the parameter
PF. The PF ranges from 0.8 leading to 0.8 lagging.
•Leading: the inverter is sourcing reac�ve power to the grid.
•Lagging: the inverter is injec�ng reac�ve power into the grid.
"PF" Mode
The reac�ve power output of the inverter varies in response to the grid voltage.
"Q(U)" Mode
The reactive power output by the inverter is controlled by the active power
of the inverter.
"Q(P)" Mode
MENU》Setup》Run Param
OK
Cancel
ActiveP 31%
ReactP 0.0%
QMode QU
PF 1.000
Fun_ISO ON
Fun_RCD ON
Island OFF
Meter ON
Limiter OFF
Feed_In 0%
MPPT Num 6
SelfCheck 20S