NAME
DESCRIPTION
Ac�veP
Adjust the output ac�ve power in %
0-110%
OFF/Q(P)/PF(P)
/Q(U)/PF/PER
ON/OFF
ON/OFF
ON/OFF
ON/OFF
0-100%
0-1000s
-1-0.8~+0.8-1
Fun_ISO
Fun_RCD
Self-check
Island
Meter
Feed_IN %
QMode
PF
Mul�ple reac�ve power control modes
Power Fator
Insula�on resistance detec�on
Residual current detec�on
Inverter's self-check �me.The default value 60s
An�-islanding protec�on
Energy meter.If inverter will connect meter,then
set here to ON
It is used to deploy how much power can be
feed in to grid when the inverter works under
zero export mode.(For example,Feed_in=50% of
the 110KW modeland loadpower is 54KW. which
means Max 55KW power can befeed into grid
a�er inverter providing 54Kw to the load firstly.
RANGE
-100%-+100%
ReactP
Adjust reac�ve power output in %
Note:
Engineer Only.
We will set the param depends on the safety requirements, so customers don't
need to reset it. The password is same as 8.23 Running param
Pic 8.24 Running Param
- 44 -