6.2 Table of supported EEP’s (EnOcean Equipment Profiles)
6.2.1 Transmit / TX
The EnOcean wireless standard defines so called EnOcean Equipment Profiles
(EEP). Each EnOcean based product sends and receives data according to at least
one standardized data format. The EnoPuck BASIC transmits data described as
follows:
Cons. nr.
EEP
Description
Tx-ID
1
A5-07-01
Occupancy sensor with supply voltage
monitor (PIR, Vibration)
EURID
Table 11: Technical data / EnOcean EEP for tx
The following table describes in detail data send by the EnoPuck BASIC according to
the EEP A5-07-01:
Offset Size Bitrange
Data
Shortcut Description Valid
range
Scale Unit
0
8
DB3.7…DB3.0 Supply
voltage
SVC
Battery
voltage
0..250
0…5.0 V
8
8
DB2.7…DB2.0 Not used (= 0)
16
8
DB1.7…DB1.0 PIR
Status
PIRS
PIR Status s.