After the burner is mounted 
 

1. Remove 

drawer 

assembly; 

2. 

Install nozzle (see specifications); 

3. Confirm 

electrode 

settings; 

4. 

Make the electrical connections; 

5. 

Complete oil line connections. 

 
 

CAUTION 

 

7

NEVER use the “interrupted ignition” function if a 
Honeywell R7184 series combustion relay is installed 
on the burner. 

 
 

CAUTION 

Do not fire the burner until you have checked the 
following: 

 
 

Checking the polarity 

 

Oil burners used on furnaces have solid state control systems which 
make them sensitive to the proper connection of the hot and neutral 
power lines. The controls will be damaged if the 2 wires are reversed. 

 

1. 

Set your voltmeter to line voltage; 

2. 

Place one prong on your grounded electric entry box and one 
prong on the black wire; 

3. Read 

the 

voltage; 

4. 

If the voltage is zero, check the white wire. If line voltage shows, 
reverse the 115-volt leads entering the furnace junction box (see 
Figure 1); 

5. 

If you do not have a voltmeter, use a pilot light. 

 

FIGURE 1 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Checking the nozzle 

 
The burner is equipped with the appropriate nozzle. However, If 
another size nozzle is required, use the manufacturer’s nozzle data 
concerning spray angle, as shown in Table 2. Note that all nozzle 
sizes are based on a pump pressure of 100 psi.  
 
Always select nozzle sizes by working back from the actual desired 
flow rate at operating pressure, and not by the nozzle marking. 

Checking air and turbulator settings 
 

Before starting the burner for the first time, adjust the air and turbulator 
settings to those listed in Table 2. Once the burner becomes 
operational, final adjustments will be necessary. 
 

Checking the fuel supply system 
 

Fuel Specifications: 
 

NOTE

: Use No.1 or No.2 Heating Oil (ASTM D396) or in Canada, use 

No.1 or No.2 Furnace Oil. 

 
 

Before starting the burner be sure the fuel tank is filled with clean oil. 

 
 

IMPORTANT 

When using nozzle sizes of less than 0.75 USGPH, the 
Installation Code for oil burning equipment requires the 
installation of a 10 micron (or less) filter in the fuel oil 
line. These instructions must be followed in order for the 
lifetime heat exchanger warranty to remain intact. 

 
 

WARNING 

 

Fire and explosion hazard. 

 

Use only approved heating type oil in this furnace. 
DO NOT USE waste oil, used motor oil, gasoline or 
kerosene. 

 

Use of these will result in death, personal injury 
and/or property damage. 

 

 
 

NOTE

: You may notice a slight odour the first time your furnace is 

operated. This will soon disappear. It is only the oil used on certain 
parts during manufacturing. 
 
 

1.8) 

BLOCKED VENT SHUT-OFF (BVSO

For chimney venting

 

 

This device is designed to detect the insufficient evacuation of 
combustion gases in the event of a vent blockage. In such a case the 
thermal switch will shut down the oil burner. The device will then need 
to be re-armed MANUALLY. 
 
Refer to the wiring diagrams and the detailed instructions supplied 
with the BVSO for the installation and wiring procedures. The length of 
wires supplied with the unit is such that the safety device must be 
installed between the flue outlet of the appliance and the draft 
regulator, as indicated in the instructions. 

DNS-0864 Rev. A 

 
It is further imperative that the BVSO be maintained annually. Refer to 
the instructions supplied with the device for more details. 
 

CAUTION 

A positive pressure venting system (Sealed Combustion 
System or Direct Vent) MUST NOT use the BVSO. Follow 
the instructions supplied with the venting system. 

 

Содержание AMT300B34-SM1PMB OLR210F19C

Страница 1: ...stries Inc Attention Do not tamper with the unit or its controls Call a qualified service technician INSTALLER SERVICE TECHNICIAN Use the information in this manual for the installation servicing of t...

Страница 2: ...low all instructions in this manual can result in personal injury and or death property damage furnace malfunction WARNING Fire hazard The furnace must be installed in a level position never where it...

Страница 3: ...Freezing temperatures and your building WARNING Freezing temperature warning Turn off water supply If your heater remains shut off during cold weather the water pipes could freeze and burst resulting...

Страница 4: ...xide gas hazard Never install a hand operated damper in the vent pipe However any Underwriters Laboratories listed electrically operated automatic type vent damper may be installed if desired Be sure...

Страница 5: ...ration into the home Home air exhausters are common Bathroom and kitchen fans power vented clothes dryers and water heaters all tend to create negative pressure in the home Should this occur the chimn...

Страница 6: ...the fuel supply system Fuel Specifications NOTE Use No 1 or No 2 Heating Oil ASTM D396 or in Canada use No 1 or No 2 Furnace Oil Before starting the burner be sure the fuel tank is filled with clean o...

Страница 7: ...m 5 must be allowed between the bottom of the coil drain pan and the top of the heat exchanger Failure to properly seal ducts can result in death personal injury and or property damage The wiring show...

Страница 8: ...pump Fire the burner Adjust the oil pressure as indicated in Table 2 2 2 2 Restart after burner failure 1 Set thermostat lower than the room temperature 2 Press the reset button on the burner primary...

Страница 9: ...urpose of the following test is to check that the electrical outlet on the furnace designated to the BVSO is functional 1 Start up the burner 2 Remove the three pole plug from the BVSO outlet on the f...

Страница 10: ...e unit 8 After cleaning replace the radiator baffles flue collar plate and oil burner 9 Readjust burner for proper operation Soot will have collected in the first sections of the heat exchanger only i...

Страница 11: ...phone Day Night Dealer name and address START UP TEST RESULTS Nozzle Pressure lb psi Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature 0 F Ambie...

Страница 12: ...40 Nozzle Delavan 1 00 70W 1 10 70W 1 25 70W Pump pressure PSIG 145 150 145 Combustion air adjustment turbulator damper 2 5 2 4 2 4 4 AFUE From CSA B21 2 standard and Canadian regulation 86 7 85 4 84...

Страница 13: ...FIGURE 3 14 Model AMT300B34 SM1PMB OLR210F19C DNS 0805 Rev C...

Страница 14: ...15 FIGURE 4 Wiring diagram AMT300B34 SM1PMB OLR210F19C heating only DNS 1017 Rev A...

Страница 15: ...16 FIGURE 4 1 Wiring diagram AMT300B34 SM1PMB OLR210F19C heating and cooling option DNS 1019 Rev A...

Страница 16: ...17 FIGURE 4 2 Ladder diagram AMT300B34 SM1PMB OLR210F19C DNS 1020 Rev A...

Страница 17: ...Rear door assembly 22 Z99F050 Recessed handle black 23 F07O001 Hexagon nut 3 8 16NC brass 24 B02753 Smoke box assembly 25 B02738 Gasket smoke box ITEM PART DESCRIPTION 26 B03349 01 Rear top panel 27 B...

Страница 18: ...on Inc Attention Ne pas alt rer votre unit ou ses contr les Appeler un technicien qualifi INSTALLATEUR TECHNICIEN Utiliser les renseignements dans ce manuel pour l installation et l entretien de l app...

Страница 19: ...ts contenus dans ce manuel s adressent un technicien qualifi exp riment dans ce type de travail au courant des pr cautions prendre des r gles de s curit respecter et muni des outils appropri s ainsi q...

Страница 20: ...iez vous procurer des extincteurs et faire installer dans votre difice ou r sidence des d tecteurs de fum e autoris s par une agence reconnue sur le plan national comme Underwriters Laboratories et le...

Страница 21: ...monoxyde de carbone de feu et d explosion Lire et suivre attentivement les instructions dans la partie suivante Si l vacuation de cette fournaise ou d autres appareils ne sont pas ad quats cela peut p...

Страница 22: ...Elle doit d passer d au moins 0 6 m 2 toute partie d difice se situant dans un rayon horizontal de 3 0 m 10 de la chemin e Elle doit se prolonger d au moins 1 5 m 5 au dessus de la derni re bride fum...

Страница 23: ...leur est de la s rie R7184 de Honeywell NE JAMAIS utiliser la fonction d allumage ignition interrompue V rification de la polarit Les br leurs au mazout utilis s avec les appareils de chauffage centr...

Страница 24: ...1 Air climatis Un climatiseur peut tre install sur l alimentation d air seulement De plus un espace minimum de 127 0 mm 5 est requis entre le dessous du serpentin de climatisation et le dessus de l ch...

Страница 25: ...our l ajustement de l appareil Effectuer les ajustements selon les sp cifications techniques contenues dans ce manuel 2 2 2 D marrage apr s d faillance du br leur 1 Ajuster le thermostat en bas de la...

Страница 26: ...rantie 2 2 7 V rification du dispositif d arr t anti refoulement BVSO Cette v rification sert valider le bon fonctionnement de la prise BVSO sur l unit de chauffage seulement 1 Faire fonctionner le br...

Страница 27: ...central 6 Nettoyer les tuyaux secondaires et le cylindre principal l aide d une brosse rigide et d un aspirateur 7 Avant le r assemblage inspecter l changeur de chaleur et la chambre de combustion afi...

Страница 28: ...technicien de service R SULTAT DU TEST DE MISE EN MARCHE Gicleur Pression lb po 2 Ajustements du br leur Bande principale Bande fine Position de la t te CO2 Indice de fum e Bacharach Temp rature des...

Страница 29: ...0 Gicleur Delavan 1 00 70W 1 10 70W 1 25 70W Pression de la pompe PSIG 145 150 145 Ajustement air combustion turbulateur volet 2 5 2 4 2 4 4 AFUE partir du standard CSA B212 et des lois canadiennes 86...

Страница 30: ...14 FIGURE 3 Mod le AMT300B34 SM1PMB OLR210F19C DNS 0805 Rev C...

Страница 31: ...15 FIGURE 4 Diagramme lectrique AMT300B34 SM1PMB OLR210F19C chauffage seulement DNS 1017 Rev A...

Страница 32: ...16 FIGURE 4 1 Diagramme lectrique AMT300B34 SM1PMB OLR210F19C chauffage et option climatisation DNS 1019 Rev A...

Страница 33: ...17 FIGURE 4 2 Diagramme en chelle AMT300B34 SM1PMB OLR210F19C DNS 1020 Rev A...

Страница 34: ...23 F07O001 ECROU HEXAGONAL A BRIDE 3 8 16NC LAITON 24 B02753 ASS SORTIE A FUMEE 25 B02738 GARNITURE SORTIE A FUMEE ITEM NUM RO DESCRIPTION 26 B03349 01 PANNEAU HAUT ARRIERE 27 B00711 FLUE BAFFLE 28 L...

Отзывы: