DS7400Xi-AT (Ver. 3+) Reference Guide Copyright © 1995-2000 Detection Systems, Inc. Page 35
9.0
How to Program the Control Panel
9.1
Entering the Programmer’s Mode
To enter the Programmer’s Mode, enter the Programmer’s Code followed by [#] [0]. Shorting the program pads (see section 2.0 for
location) on the control panel will also activate Programmer’s Mode. The default Programmer’s Code is [9] [8] [7] [6].
9.2
Reading back a Program Address
Once you are in the programmer’s mode, to read back the value of a Program Address, enter that Program Address followed by [#]. Each
data digit is displayed one data digit at a time. To view the second data digit, enter the [#] button again.
The display will look like this:
9.3
Entering a value in a Program Address
To enter a value in the Program Address, enter the Program Address, then enter the value for each Data Digit, then enter [#] to save it and
move on to the next Program Address. Entering data digit 1 will increment you to the next data digit.
The display will show the Program Address and will display the value of each Data Digit after you enter it. The data will be programmed
(saved) when you press the [#] key. The control panel will automatically increment to the next program address.
• If you wish to program that next address, enter the necessary information.
• If you wish to read back the value of that address, press the [#] key.
• If you wish to program a different address, press the [*] key two times and enter the program address you wish to program.
If you make a mistake at any time, press the [*] key two times (before pressing the [#] key). This will clear the display, allowing you to enter
the program address you wish to work with.
9.4
HEX values
Some Data Digit values will be higher than 9. These values must be programmed by pressing the [*] key followed by some other number.
These values will display as HEX characters (A - F) when entered. Example: entering *0 at the keypad will display an A.
The HEX character values are as follows:
*0 = A
*1 = B
*2 = C
*3 = D
*4 = E
*5 = F
9.5
Defaults
The DS7400Xi is shipped from the factory as a working, pre-programmed control. Many of the programming addresses may already be
set to the values you need. The default values are shown in
If the value you would like is in , you don’t need to re-program this address.
In the example below, a “0” is the default value:
If the default value is not shown in reverse print, it will be shown in a separate table.
9.6
Setting the Control to the Factory Default
Only enter [0] [1] [#] in Program Address 4058 when you are completely sure you want to erase all installer programming.
Entering [0] [1] [#] in Program Address 4058 will immediately reset the control to the factory default. Any programming
already done by the installer will be erased. This action cannot be reversed.
To set the control’s programming values back to the default, enter the programming mode, then enter [4] [0] [5] [8] [0] [1] [#].
9.7
Exiting the Programmer’s Mode
To exit the Programmer’s Mode, press the [*] key for a minimum of 2 seconds. If no keypad entries are made for 4 minutes, the control will
automatically exit you from the Programmer’s Mode.
Reverse Print
Reverse Print
Содержание DS7400Xi-AT
Страница 11: ...DS7400Xi AT Ver 3 Reference Guide Copyright 1995 2000 Detection Systems Inc Page 11 5 0 System Worksheet...
Страница 76: ...DS7400Xi AT Ver 3 Reference Guide Copyright 1995 2000 Detection Systems Inc Page 76 Pager Format Continued...
Страница 78: ...DS7400Xi AT Ver 3 Reference Guide Copyright 1995 2000 Detection Systems Inc Page 78 14 1 SIA Formats Continued...
Страница 79: ...DS7400Xi AT Ver 3 Reference Guide Copyright 1995 2000 Detection Systems Inc Page 79 14 2 CID Formats...
Страница 94: ...DS7400Xi AT Ver 3 Reference Guide Copyright 1995 2000 Detection Systems Inc Page 94 Installation Notes...
Страница 95: ...DS7400Xi AT Ver 3 Reference Guide Copyright 1995 2000 Detection Systems Inc Page 95 Installation Notes...
Страница 96: ...DETECTION SYSTEMS INC...