![Detcon MCX-32-N1P Скачать руководство пользователя страница 49](http://html1.mh-extra.com/html/detcon/mcx-32-n1p/mcx-32-n1p_operators-installation-and-instruction-manual_2487586049.webp)
Model MCX-32
Model MCX-32 Instruction Manual
Rev. 2.3
Page 43 of 49
11.0
Specifications
Capacity
User Configurable
Up to 64 4-20mA analog or serial inputs
Inputs
RS-485 Modbus
™
RTU
Analog 4-20mA (using DA-4 Modules)
Outputs
User Configurable:
Form C Relay Contacts (using RL-4 Modules)
4-20mA outputs (using AO-4 Modules)
Standard: RS-485 Modbus
™
RTU
Accuracy/Repeatability
Display: < 1% Full Scale
DA-4: < 1% Full Scale
AO-4: < 1% Full Scale
Power Input
110-230VAC
20-30VDC
Power Consumption
Base MCX-32 Controller: 20 Watts at 24VDC
Total Power consumption is dependent on number of I/O modules, number of gas sensors, and the type of
gas sensors
Total power of controller with I/O modules and gas sensors not to exceed 120 Watts (5A at 24VDC)
Display
5.8” Diagonal Graphic Backlit LCD with Touch Screen
Electrical Classification
NEMA 1 (MCX-32-N1P), NEMA 4X (MCX-32-N4X)
Dimensions
MCX-32-N1P – 10.5”W x 8”H x 13''D
MCX-32-N4X – 14.25”W x 14.25”H x 8.2''D
Operating Temperature Range
0°C to +50°C
Warranty
One year