![Detcon MCX-32-N1P Скачать руководство пользователя страница 33](http://html1.mh-extra.com/html/detcon/mcx-32-n1p/mcx-32-n1p_operators-installation-and-instruction-manual_2487586033.webp)
Model MCX-32
Model MCX-32 Instruction Manual
Rev. 2.3
Page 27 of 49
Figure 27
Power Management Screen
The controller has the unique ability to provide a charging voltage for batteries. If batteries are connected to
the auxiliary 24VDC input, this feature will provide a nominal 27VDC @ 1Amp (maximum) to the auxiliary
24VDC input to charge the batteries. The circuit will monitor the batteries and keep the batteries at full
charge. Once the batteries have been connected to the auxiliary 24VDC input terminals, touch DC POWER
on the secondary side of the screen to enable the MCX-32’s battery charging circuitry. DC POWER will
change to BATTERY which will enable the battery charging circuitry and apply the charging voltage to the
auxiliary 24VDC input terminals.
NOTE:
The battery charging feature
should not
be enabled for external 24VDC power sources
or battery backup units that provide their own charging circuitry.
WARNING:
Switching the secondary from DC POWER to BATTERY with a hard line DC power
source connected to the auxiliary 24VDC input may result in damage to the MCX-32 Controller. This
also includes battery backup units that have their own charging circuitry.
Figure 28
Power Management with Battery Charge ‘ON’
When the battery feature is selected, DC POWER will change to BATTERY and if the battery charging circuit
senses that the batteries need charging, CHARGING will appear below BATTERY, and both will be
highlighted. The voltage displayed on the Secondary side will then reflect the charging voltage provided to the
batteries.