Model MCX-32
Model MCX-32 Instruction Manual
Rev.2.3
Page 4 of 49
2.0
Installation (N1P Enclosure)
2.1 Mounting and Cable Installation
The Model MCX-32-N1P controller is housed in a NEMA 1 panel mount enclosure for indoor use. Securely
mount the Model MCX-32-N1P per the mounting dimensions provided in Figure 1. The enclosure is designed
to fit a panel opening of 9.25” wide by 7.5” high. Keep AC power separate from DC power and signals within
conduit runs.
3.5"
8"
9.75"
10.5"
8"
HOME
AL ARM
AL ARM
SILENCE
RESET
ALARM
INHIBIT
Allow at least 13" of
Clearance for wiring
0.218"
0.375"
R0.109"
Slot Detail
I/O Modules
(Qty. of 2 Max)
Figure 1
MCX-32-N1P Controller Mounting and Dimensional View
2.2 Power Connections
The Model MCX-32-N1P controller can be powered by 110/220VAC, 20-30VDC or both. An internal power
supply is available for the MCX-32-N1P that converts 110/220VAC to 24VDC (up to 5Amps) and can power
up to 32 sensors and any associated I/O modules. The MCX-32 controller can also be powered by an external
DC source that meets the input requirements of the unit if AC power is not available or desired.
NOTE:
The power supply for the MCX-32-N1P controller can power up to a maximum of 32
sensors and any associated I/O modules even though the controller is capable of
communication with up to 64 devices.
An additional power supply will be required if
powering more than 32 sensors.
NOTE:
The MCX-32-N1P controller can accommodate only 2 I/O modules. Any additional
modules required will need to be mounted in a separate enclosure by the customer.
2.2.1
AC Power
Connect 110/220VAC input wiring to the terminals located on the back of the enclosure, labeled “VAC (L1)”,
“NEU (L2)”, and “GROUND” (See Figure 2). The power supply for the MCX-32-N1P is capable of handling
AC inputs from 100-240VAC, 50-60Hz without degradation.