F-3
95-8676
3.1
Device Configuration (Read/Write)
This area of memory holds field adjustable parameters for the device. The Hart configuration changed bit will be set
on writes to this area.
Eclipse Device Configuration
Description
Address
Value
Modbus Polling Address
40101
1..247
Baud Rate Code
40102
See Codes
Parity Code
40103
See Codes
Gas Type
40104
See Codes
Calibration Gas Type
40105
See Codes
Calibration Method
40106
See Codes
Calibration Cuvette Length
(1.0 to 150.0 mm)
40107
Float LSW
40108
Float MSW
Analog Fault Code
40109
See Codes
4 to 20 Range
(0 to 2%/vol)
40110
Float LSW
40111
Float MSW
Cal Gas Concentration
(1%/vol)
40112
Float LSW
40113
Float MSW
Warmup Fault Level
(0.0 to 24.0 mA)
40114
Float LSW
40115
Float MSW
Blocked Optics Fault Level
(0.0 to 24.0 mA)
40116
Float LSW
40117
Float MSW
Calibration Current Level
(0.0 to 24.0 mA)
40118
Float LSW
40119
Float MSW
General Fault Current Level
(0.0 to 24.0 mA)
40120
Float LSW
40121
Float MSW
Volume in %/vol
(Special Gas Type)
40122
Float LSW
40123
Float MSW
Low Alarm Level
(5 to 50% of scale)
40134
Float LSW
40135
Float MSW
High Alarm Level
(10 to 60% of scale)
40136
Float LSW
40137
Float MSW
Low Alarm Latch
40138
See Codes
High Alarm Latch
40139
See Codes
Reserved
40140
NOTE
Refer to “Alarm Relays” in the
Specifications section of this manual for
important information regarding alarm
relays.