F-6
95-8676
3.1
Fault Status Word
These bits are used to signal the active faults of the device.
Control Words
Setting values in this area of memory initiates action in the device. For example, it may start a calibration sequence.
The device automatically clears command word bits after the function is performed.
Name
Bit
Calibration Fault
0
Dirty Optics
1
Open Lamp
2
Cal Active at start
3
EE Error 1
4
EE Error 2
5
Ref ADC Saturated
6
Active ADC Saturated
7
Bad 24 volts
8
Bad 12 volts
9
Bad 5 volts
10
Zero Drift
11
Flash CRC Error
12
Ram Error
13
Eclipse Control Words
Description
Address
Value
Command Word 1
40301
See below
Command Word 2 (Reserved)
40302
Reserved
40303
to
40306