3.1.13. Smoke Alarm
This is an Automatic Reset Alarm. The Smoke Alarm is activated when the smoke
alarm contact opens. In this state the unit will stop and not restart until the smoke
alarm contact closes. The red ALARM LED on the display will stay lit until the alarm
is
reset.
3.1.14. Low Air Flow
This is a Manual Reset alarm. The Low Air Flow failure is activated when the air flow
drops below acceptable levels. For more information on this condition refer to section
2.6.1.4. In this state the unit will stop and not restart until the alarm condition is reset
manually. The red ALARM LED on the display will stay lit until the alarm is reset.
3.1.15 Freeze ‘Stat Alarm
This is a Manual Reset alarm. The Freeze ‘Stat Alarm is activated when the
temperature across the water coils drops. In this state the unit will stop and not
restart until the alarm condition is reset manually. The red ALARM LED on the
display will stay lit until the alarm is reset.
3.1.16 Condenser Fan Overload
This is an Automatic Reset alarm. The Condenser Fan Overload is activated when any
of the four condenser fan overload devices trip. The unit will continueto run, the red
ALARM LED on the display will stay lit until the alarm is reset.
3.1.17 High Discharge Temperature Alarm
This is a Manual Reset alarm. The High Discharge Temperature Alarm is activated
when the compressor temperature rises to an unacceptable level. In this state the unit
will stop and not restart until the alarm condition is reset manually. The red ALARM
LED on the display will stay lit until the alarm is reset.
3.1.18 High Superheat Alarm
This is a Manual Reset alarm. The High Superheat Alarm is activated the superheat
rises to an unacceptable level. In this state the unit will stop and not restart until the
alarm condition is reset manually. The red ALARM LED on the display will stay lit until
the alarm is reset.
3.1.19 Low Oil Level Alarm
This is a Manual Reset alarm. The Low Oil Level Alarm is activated when the variable
speed compressor oil level drops to an unacceptable level. In this state the unit will
stop and not restart until the alarm condition is reset manually. The red ALARM LED
on the display will stay lit until the alarm is reset.
3.1.20 Modbus Fault
This is a Manual Reset alarm. The Modbus Fault is activated when the c. PCOe
expansion board is required by the system, but communication had not been
Desert Aire - CM3500 Manual
Содержание CM3500 Series
Страница 2: ...2 ...
Страница 5: ...5 Desert Aire CM3500 Manual Product Warning for the State of California ...
Страница 6: ...6 Desert Aire CM3500 Manual ...
Страница 10: ...10 Desert Aire CM3500 Manual ...
Страница 16: ...16 Desert Aire CM3500 Manual ...
Страница 60: ...60 Desert Aire CM3500 Manual ...
Страница 66: ...66 Desert Aire CM3500 Manual ...
Страница 78: ...78 Desert Aire CM3500 Manual Figure 89 Addressing is now complete ...
Страница 79: ...79 Desert Aire CM3500 Manual ...