56
Figure 63
The Condenser Fan Overload Count screen is shown in Figure 64. The count
is a running tally provided for troubleshooting the fan motor. Refer to the unit
wiring to determine if the condenser fan motors include this option. After a motor
has been serviced, pressing the
Prg
key will reset all of the counts back to zero.
To return to the Parameter Settings, press the
Esc
key.
Figure 64
2.6.3. Sensor Offsets (Figures 65 - 66)
These screens allow for the control values of the analog input points to be adjusted if calibration
shows these devices to be inaccurate. More than one Sensor Offset screen may be provided
depending upon the optional equipment included with your dehumidifier. Pressing the
UP
or
DOWN
keys from the first Sensor Offset Screen, Figure 65, will cycle through all applicable screens. The
range of these offsets is -99.9 to 99.9 for the refrigerant pressures, temperatures and humidity. The
range for the air pressure and CO
2
sensors is -99 to 99.
Desert Aire - CM3500 Manual