35
range setting, the highest SAT Set Point will be used. When the outside air temperature
falls between the low setting and the medium setting, the second highest SAT Set
Point will be used. When the outside air temperature falls between the medium setting
and the high setting, the second lowest SAT Set Point will be used. When the outside
air temperature rises above the high setting, the lowest SAT Set Point will be used.
This screen will only be shown if the Outside Air Reset option is selected. This screen
allows the Outside Air Low, Medium and High Set Points as well as the four SAT
Set Points to be modified. The range of all set points on this screen is 55º to 95.0º F.
However, the Outside Air Low Setting cannot be greater than the Outside Air Medium
Setting. The Outside Air Medium Setting cannot be less than the Outside Air Low
Setting and it cannot be greater than the Outside Air High Setting. Lastly, the Outside
Air High Setting cannot be less than the Outside Air Medium Setting. Also, the highest
SAT Set Point cannot be set lower than the second highest SAT Set Point. The second
highest SAT Set Point cannot be set higher than the highest SAT Set Point and lower
than the second lowest SAT Set Point. The second lowest SAT Set Point cannot be
set higher than the second highest SAT Set Point and lower than the lowest SAT Set Point.
The lowest SAT Set Point cannot be set higher than the second lowest SAT Set Point.
To modify the set points, press the
ENTER
key and use the arrow keys until the
desired setting is shown. Press the
ENTER
key to accept set point value.
To return to the TEMPERATURE SETTINGS MENU, press the
Esc
key.
Figure 30
2.4.6. Unoccupied Settings (Figure 31)
This screen will only be shown if the Zone Reset and the Unoccupied Control is
selected in for the unit. These set points will only be used in the unoccupied mode.
The range of the Cooling Set Point is from the current Heating Set Point setting to
95.0º F with a default of 65.0º F. The range of the Heating Set Point is from 40.0º F to
the current Cooling Set Point setting with a default of 85.0º F. To modify the set point,
press
the
ENTER
key and use the arrow keys until the desired setting is shown. The
range of the Unoccupied Humidity Set point is 20.0% to 99.9%, with a default of 60.0%.
Desert Aire - CM3500 Manual
Содержание CM3500 Series
Страница 2: ...2 ...
Страница 5: ...5 Desert Aire CM3500 Manual Product Warning for the State of California ...
Страница 6: ...6 Desert Aire CM3500 Manual ...
Страница 10: ...10 Desert Aire CM3500 Manual ...
Страница 16: ...16 Desert Aire CM3500 Manual ...
Страница 60: ...60 Desert Aire CM3500 Manual ...
Страница 66: ...66 Desert Aire CM3500 Manual ...
Страница 78: ...78 Desert Aire CM3500 Manual Figure 89 Addressing is now complete ...
Страница 79: ...79 Desert Aire CM3500 Manual ...