13
Desert Aire dehumidifiers ordered with the CO
2
control package require sensors
for the indoor and outdoor CO
2
levels. These measurements are used to determine
the
CO
2
differential level in the conditioned space. This differential is the variable
compared to the CO
2
set point and used in the control loop to provide more or less
outdoor air into the conditioned space.
The outdoor CO
2
sensor is installed in a protective enclosure and is designed to
operate in outdoor conditions ranging from -40° F to 158° F. 24VAC power is
required for this device and the output is 4-20mA. (See your wiring schematic for
connection
details.)
The indoor CO
2
sensor is installed in a high impact ABS enclosure and has an
operating temperature range of 32° F to 122° F. 24VAC power is required for this
device and the output is 4-20mA. (See your wiring schematic for connection details.)
CAUTION:
Do not run sensor wiring adjacent to, OR in the same conduit as, wires
carrying more than 24 VAC.
1.3. Auxiliary Air Heating Control Wiring
Note: You must use the Desert Aire CM3500 control system to control or interlock with the
room heating system. This prevents wide fluctuations in room air temperature. It also
prevents the heater from trying to heat the room while the dehumidifier is running in the
cooling mode.
1.3.1. Auxiliary Heating - Dry Contact Closure
The standard Desert Aire CM3500 Controller provides a dry contact closure to
operate the auxiliary space heater. The contact closes to energize a heater (may
be supplied by others) which has its own power source.
Install two wires from the thermostat terminal blocks on the heater to the terminal
strip on the control panel of the dehumidifier. (See your wiring schematic for
connection
details.)
1.3.2. Auxiliary Heating - Proportional Signal
As an option, Desert Aire will provide a proportional 0-10 VDC direct-acting signal
to modulate a heating coil control valve or other auxiliary modulating heater. Most
proportional valves have either three (3) or four (4) terminals for field-installed
wiring.
• Four-terminal valves have two terminals for 24 VAC power and two terminals
for the signal input.
• Three-terminal valves have one terminal for the “hot” 24 VAC input, a second
terminal for the “positive” signal input and a third, common terminal for the
“neutral” 24 VAC input and the “negative” signal input.
Desert Aire - CM3500 Manual
Содержание CM3500 Series
Страница 2: ...2 ...
Страница 5: ...5 Desert Aire CM3500 Manual Product Warning for the State of California ...
Страница 6: ...6 Desert Aire CM3500 Manual ...
Страница 10: ...10 Desert Aire CM3500 Manual ...
Страница 16: ...16 Desert Aire CM3500 Manual ...
Страница 60: ...60 Desert Aire CM3500 Manual ...
Страница 66: ...66 Desert Aire CM3500 Manual ...
Страница 78: ...78 Desert Aire CM3500 Manual Figure 89 Addressing is now complete ...
Страница 79: ...79 Desert Aire CM3500 Manual ...